The TM210 thermal-magnetic release provides fixed overload and short-circuit protection curves. At 415 V AC the interrupting rating is 76 kA, still ample for most industrial service-entrance applications.
Rated current holds at 32 A from 40 °C through 50 °C ambient, then gradually declines: 31 A at 55 °C, 31 A at 60 °C, 30 A at 65 °C, and 30 A at 70 °C. In a warm enclosure with other heat sources, expect to apply the 55 °C derating figure if the internal ambient exceeds 50 °C.
The breaker occupies 50.8 mm width (2 in) per pole — a 2-pole unit fits a 2-inch wide DIN-rail slot. Depth is 70 mm (2.76 in), height 130 mm (5.12 in). Front-face protection is IP40, meaning tools or fingers won't contact live parts from the front, but the sides and back are not sealed against dust ingress.
For BOM freeze or line-down replacement, the 3VM1132-4ED22-0AA0 is sourced to order through independent distribution channels against an RFQ.