Skip to main content
Siemens 3VM1150-3EE46-0AA2 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VM1150-3EE46-0AA2 MCCB, 4-Pole, 50 A, 76 kA

MPN3VM1150-3EE46-0AA2

Siemens SENTRON 3VM1150-3EE46-0AA2, 4-pole molded case circuit breaker, 50 A rated at 40 °C, TM220 release, 76 kA interrupting at 240 V, 70 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1150-3EE46-0AA2 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VM1150-3EE46-0AA2 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V12 kA
Power loss, max.15 W
3VM1150-3EE46-0AA2 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VM1150-3EE46-0AA2 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1150-3EE46-0AA2 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1150-3EE46-0AA2 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1150-3EE46-0AA2 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

What this 4-pole MCCB delivers

Its TM220 thermal-magnetic release provides overload and short-circuit protection, with a rated current of 50 A at 40 °C that holds flat through 50 °C before a gentle derate begins — 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. That thermal stability means you can load it near nameplate in a warm panel without forced derating. Interrupting capacity is rated per voltage: 76 kA at 240 V, 53 kA at 415 V, 32 kA at 440 V, and 12 kA at 500 V. The 76 kA at 240 V figure is the headline — it handles high-fault scenarios on 240 V distribution without cascading upstream. The 53 kA at 415 V covers the common three-phase industrial voltage.

Form factor and panel fit

Dimensions: 70 mm depth, 101.6 mm width, 130 mm height. Width at 101.6 mm (4 inches) is the standard 4-pole MCCB footprint; it occupies four 25 mm DIN spaces if mounted on a DIN rail adapter.

Rated insulation voltage: 800 V. Overcurrent release design: TM220 (thermal-magnetic, fixed thermal and magnetic settings). Power loss at rated load: 15 W maximum. Storage temperature: -40 °C to 80 °C. Trip indicator is not present — visual trip indication is via the handle position only.

Frequently asked questions

What is the closest functional second-source to 3VM1150-3EE46-0AA2?

The closest functional peer is the 3VA1110-5ED36-0AC0, also a 4-pole SENTRON MCCB. The delta is in the release design and interrupting ratings — the 3VA series uses a different trip unit platform (electronic vs TM220 thermal-magnetic). Verify the interrupting capacity at your system voltage and the trip curve before substituting; the 3VM series is the economy line, the 3VA series is the full-featured line with higher interrupting options and electronic trip units.

Will 3VM1150-3EE46-0AA2 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?

Form factor is the same — both are 4-pole SENTRON MCCBs with the same 70 mm depth, 101.6 mm width, and 130 mm height. The mounting hole pattern and bus bar spacing are identical across the 3VM and 3VA families. No rewiring is needed for the same ampacity and pole count, but check the interrupting capacity at your fault level: the 3VA series typically offers higher kA ratings than the 3VM economy line.

Where can I buy 3VM1150-3EE46-0AA2 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ with your target quantity and delivery window; we will confirm availability and current pricing at quote time. No minimum order quantity restrictions apply.

What compliance documentation does Siemens provide for 3VM1150-3EE46-0AA2?

Siemens SENTRON MCCBs are typically supplied with CE marking, RoHS compliance, and IEC 60947-2 certification. The specific declarations and test reports are available from Siemens Industry Online Support under the 3VM product documentation. For UL/CSA listings, verify the specific variant — the 3VM series is primarily IEC-rated; the 3VA series carries UL 489 listing.

MPN
3VM1150-3EE46-0AA2