Skip to main content
Siemens 3VM1150-3EE36-0AA2 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1150-3EE36-0AA2 SENTRON MCCB, 50 A, 500 A max, 76

MPN3VM1150-3EE36-0AA2

Siemens SENTRON 3VM1150-3EE36-0AA2, molded case circuit breaker, 3-pole, TM220 release, 50 A (40 °C), 500 A frame, 76 kA at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1150-3EE36-0AA2 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VM1150-3EE36-0AA2 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V12 kA
Power loss, max.15 W
3VM1150-3EE36-0AA2 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VM1150-3EE36-0AA2 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1150-3EE36-0AA2 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1150-3EE36-0AA2 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1150-3EE36-0AA2 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

It carries a continuous current rating of 50 A at 40 °C and a maximum frame rating of 500 A, with interrupting capacities of 76 kA at 240 V AC, 53 kA at 415 V AC, 32 kA at 440 V AC, and 12 kA at 500 V AC. The 50 A rating holds flat through 50 °C — no derating needed in a warm panel — then steps down to 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. That thermal curve means a panel builder can size the branch at a full 50 A without over-speccing for typical enclosure ambient temperatures.

The breaker measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling. Maximum power dissipation is 15 W at full load — account for that heat in the enclosure thermal budget when grouping multiple breakers.

Frequently asked questions

What are the interrupting ratings for 3VM1150-3EE36-0AA2 at different voltages?

The breaker is rated 76 kA at 240 V AC, 53 kA at 415 V AC, 32 kA at 440 V AC, and 12 kA at 500 V AC. These are the maximum short-circuit currents it can safely interrupt at each voltage level.

Where can I buy 3VM1150-3EE36-0AA2?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

What is the thermal derating for 3VM1150-3EE36-0AA2 above 40 °C?

The 50 A rating holds through 50 °C. At 55 °C it derates to 49 A, at 60 °C to 48 A, at 65 °C to 46 A, and at 70 °C to 45 A.

MPN
3VM1150-3EE36-0AA2