Skip to main content
Siemens 3VM1180-3ED12-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1180-3ED12-0AA0 SENTRON MCCB, 1-pole 80 A, 53 kA

MPN3VM1180-3ED12-0AA0
Active

Siemens SENTRON 3VM1180-3ED12-0AA0, 1-pole molded case circuit breaker, 80 A, TM210 thermal-magnetic release, 53 kA at 240 V AC, 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VM1180-3ED12-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VM1180-3ED12-0AA0 — Ratings
ParameterValue
Number of poles1
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classN
Breaking capacity at 240 V53 kA
Breaking capacity at 415 V7.5 kA
Power loss, max.6.4 W

Protection & Trip Unit

3VM1180-3ED12-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VM1180-3ED12-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40

Accessories & Functions

3VM1180-3ED12-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VM1180-3ED12-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VM1180-3ED12-0AA0 — Mechanical
ParameterValue
Height130 mm
Width25.4 mm
Depth70 mm
Height (in)5.1 in
Width (in)1 in
Depth (in)2.8 in

Product details

1-pole MCCB for line protection — 80 A, 53 kA at 240 V

The Siemens SENTRON 3VM1180-3ED12-0AA0 is a 1-pole molded case circuit breaker rated 80 A continuous at 40 °C, with a TM210 thermal-magnetic release (fixed Ir = 80 A, adjustable Ii = 800 A). It delivers 53 kA interrupting capacity at 240 V AC and 7.5 kA at 415 V AC, making it a fit for high-fault service-entrance or distribution panels where the upstream transformer can deliver heavy short-circuit current.

Thermal derating and operating range

The breaker holds its full 80 A rating from 40 °C up to 50 °C. Above that, it derates gradually: 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. The maximum operating ambient is 70 °C, with storage from -40 °C to 80 °C. That thermal curve matters if the breaker lives in a crowded, poorly ventilated enclosure — plan for the actual panel ambient, not the nameplate.

Mechanical fit and panel integration

At 25.4 mm wide (one standard pole pitch), 130 mm tall, and 70 mm deep, this breaker snaps onto a DIN rail or mounts directly in a distribution panel. The front face carries an IP40 protection class — suitable for dry indoor enclosures but not washdown areas. Rated insulation voltage is 500 V AC; maximum DC operating voltage is 125 V. Power dissipation at rated load is 6.4 W, so factor that into the enclosure thermal budget.

Frequently asked questions

How do I get current pricing and availability for 3VM1180-3ED12-0AA0?

Submit an RFQ through this listing; pricing and stock are confirmed at quote time through independent distribution channels.

What is the interrupting capacity of 3VM1180-3ED12-0AA0 at 240 V?

It is rated 53 kA at 240 V AC, and 7.5 kA at 415 V AC.

MPN
3VM1180-3ED12-0AA0