Skip to main content
Siemens 3VM1180-3GE42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VM1180-3GE42-0AA0 4-Pole MCCB, 80 A, 76 kA

MPN3VM1180-3GE42-0AA0
Active

Siemens SENTRON 3VM1180-3GE42-0AA0, 4-pole molded case circuit breaker, 80 A, TM220 release, 76 kA at 240 V AC, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1180-3GE42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1180-3GE42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V12 kA
Power loss, max.19 W
3VM1180-3GE42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1180-3GE42-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1180-3GE42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1180-3GE42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1180-3GE42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

Line protection MCCB with TM220 release

The Siemens SENTRON 3VM1180-3GE42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying 80 A continuously up to 50 °C ambient and derating to 74 A at 70 °C — the full thermal curve means no guesswork when the panel runs hot. Breaking capacity climbs with voltage: 76 kA at 240 V AC, 53 kA at 415 V, 32 kA at 440 V, and 12 kA at 500 V — that spread covers most industrial LV distribution boards without an upstream current-limiting fuse.

Thermal performance and panel fit

At 80 A the maximum power loss is 19 W — modest enough that standard DIN-rail or base-mount spacing in a ventilated enclosure handles the heat without forced cooling. The 4-pole width (101.6 mm) matches the standard 4-module MCCB footprint for panel cutouts and busbar layouts.

Frequently asked questions

What is the breaking capacity of 3VM1180-3GE42-0AA0 at different voltages?

76 kA at 240 V AC, 53 kA at 415 V AC, 32 kA at 440 V AC, and 12 kA at 500 V AC.

Where can I buy 3VM1180-3GE42-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the rated current and thermal derating for 3VM1180-3GE42-0AA0?

Rated 80 A at 40–50 °C, derating to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C.

MPN
3VM1180-3GE42-0AA0