Skip to main content
Siemens 3VM1180-4ED22-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1180-4ED22-0AA0 SENTRON MCCB, 80 A, 2-Pole, 121 k

MPN3VM1180-4ED22-0AA0
Active

Siemens SENTRON 3VM1180-4ED22-0AA0, molded case circuit breaker, 2-pole, 80 A at 40 °C, 121 kA at 240 V, TM210 release, switching capacity class S.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1180-4ED22-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1180-4ED22-0AA0 — Ratings
ParameterValue
Number of poles2
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Power loss, max.13 W
3VM1180-4ED22-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1180-4ED22-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1180-4ED22-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1180-4ED22-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1180-4ED22-0AA0 — Mechanical
ParameterValue
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.1 in
Width (in)2 in
Depth (in)2.8 in

Product details

It carries an 80 A continuous current at 40 °C, with a thermal-magnetic TM210 overcurrent release providing LI (long-time and instantaneous) protection. The switching capacity class S rating means it delivers 121 kA at 240 V AC and 76 kA at 415 V AC — figures that govern its ability to safely interrupt fault currents without upstream cascading.

Rated current holds at 80 A from 40 °C through 50 °C, then derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. Operating ambient range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. Maximum power loss is 13 W.

Dimensions are 130 mm height, 50.8 mm width, 70 mm depth. The 2-pole width at 50.8 mm (2 inches) matches standard DIN-rail or panel-mount cutout spacing for SENTRON MCCBs. Front IP40 protection covers the operator interface; the breaker is not sealed for washdown environments.

Frequently asked questions

What is the breaking capacity of 3VM1180-4ED22-0AA0 at 240 V?

At 240 V AC the breaking capacity is 121 kA; at 415 V AC it is 76 kA.

Where can I buy 3VM1180-4ED22-0AA0?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 3VM1180-4ED22-0AA0 drop into a panel specified around 3VA1110-5EF36-0AD0?

The 3VM1180-4ED22-0AA0 is a 2-pole 80 A MCCB with a 50.8 mm width, while the 3VA1110-5EF36-0AD0 is a different variant; verify the mounting footprint and bus-bar spacing against the panel layout before substitution.

MPN