Skip to main content
Siemens 3VM1180-4ED42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1180-4ED42-0AA0 SENTRON MCCB, 80 A, 4-Pole, 121 k

MPN3VM1180-4ED42-0AA0
Active

Siemens SENTRON 3VM1180-4ED42-0AA0, molded case circuit breaker, 4-pole, 80 A, TM210 thermal-magnetic release, 121 kA at 240 V AC, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VM1180-4ED42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VM1180-4ED42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V53 kA
Breaking capacity at 500 V12 kA
Power loss, max.19 W

Protection & Trip Unit

3VM1180-4ED42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VM1180-4ED42-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40

Accessories & Functions

3VM1180-4ED42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VM1180-4ED42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VM1180-4ED42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

What this MCCB delivers on the line

The Siemens SENTRON 3VM1180-4ED42-0AA0 is a 4-pole molded case circuit breaker rated 80 A continuous at 40 °C, with a TM210 thermal-magnetic release for line protection. Its interrupting capacity hits 121 kA at 240 V AC, 76 kA at 415 V, 53 kA at 440 V, and 12 kA at 500 V — numbers that define the available fault current it can safely clear at the point of installation. The 800 V rated insulation voltage (Ui) and 690 V max AC operating voltage cover most industrial distribution panels. IP40 on the front means it's protected against solid objects over 1 mm but not sealed against moisture; mount it inside a suitable enclosure. Current rating holds flat at 80 A from 40 °C through 50 °C, then derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. If your panel ambient runs above 50 °C, factor that derating into the load schedule — the breaker won't trip early, but continuous current capability drops.

Panel fit and mounting

Dimensions are 101.6 mm wide, 130 mm high, 70 mm deep — a 4-pole MCCB footprint that fits standard Siemens SENTRON panel cutouts and busbar systems.

MPN
3VM1180-4ED42-0AA0