Skip to main content
Siemens 3VM1196-3ED26-0AA2 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1196-3ED26-0AA2 Circuit Breaker, 25kA @ 415V, 16A

MPN3VM1196-3ED26-0AA2

Siemens 3VM1 IEC frame 160, breaking capacity class N, 2-pole circuit breaker, Icu=25kA @ 415V, TM210 line protection, In=16A, Ir=16A, Ii=20 x In, terminal connection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

Circuit Breaker 3VM1196-3ED26-0AA2 – Key Ratings and Fit

The Siemens 3VM1196-3ED26-0AA2 is a 2-pole IEC frame 160 circuit breaker from the 3VM1 series, rated for breaking capacity class N with an Icu of 25 kA at 415 V AC. This means it can safely interrupt fault currents up to 25,000 A without damage, which is the standard requirement for most industrial distribution panels and motor control centers in a 400 V class installation. The 16 A fixed thermal overload setting (Ir=16 A, not adjustable) and the fixed magnetic short-circuit release at 20 x In (320 A) make it a line-protection device suited for feeder circuits or as a main disconnecting means for a fixed-load group, not for motor overload protection where adjustable trip curves are needed.

Deployment Context – Panel Integration

Mounts on a standard DIN rail in an enclosure. The 2-pole form factor occupies two module widths (approximately 36 mm per pole). Terminal connection type accepts copper conductors per IEC 60947-1; verify lug size against the panel's busbar or cable entry plan. The 25 kA SCCR at 415 V means it can be used in a panel with a fault current rating up to that level without requiring a current-limiting upstream device, simplifying coordination studies.

Frequently asked questions

What is the breaking capacity of this circuit breaker?

The Icu (ultimate breaking capacity) is 25 kA at 415 V AC, per the IEC 60947-2 standard for breaking capacity class N.

Where can I buy 3VM1196-3ED26-0AA2?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the overload protection setting on this breaker?

The thermal overload protection is fixed at Ir = 16 A (not adjustable). The short-circuit magnetic release is fixed at Ii = 20 x In, or 320 A.

MPN
3VM1196-3ED26-0AA2