Skip to main content
Siemens 3VM1196-5ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VM1196-5ED32-0AA0 MCCB, 3-pole, 16 A, 187 k

MPN3VM1196-5ED32-0AA0
Active

Siemens SENTRON 3VM1196-5ED32-0AA0, 3-pole molded case circuit breaker, 16 A rated current, TM210 release, 187 kA at 240 V, 121 kA at 415 V, 76 kA at 440 V, 17 kA at 500 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VM1196-5ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VM1196-5ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V76 kA
Breaking capacity at 500 V17 kA
Power loss, max.11 W

Protection & Trip Unit

3VM1196-5ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VM1196-5ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40

Accessories & Functions

3VM1196-5ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VM1196-5ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VM1196-5ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Molded Case Circuit Breaker for Line Protection

The Siemens SENTRON 3VM1196-5ED32-0AA0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection, carrying a rated current of 16 A across its operating range from -25 °C to 70 °C, with a rated insulation voltage of 800 V. Its TM210 thermal-magnetic release handles overloads and short circuits, with a maximum breaking capacity of 187 kA at 240 V AC, 121 kA at 415 V, 76 kA at 440 V, and 17 kA at 500 V — the numbers drop as system voltage rises, so the 415 V figure is the one to size against for common industrial distribution panels.

Thermal Derating and Panel Fit

The 16 A rating holds steady from 40 °C through 55 °C, then derates to 15 A at 60 °C through 70 °C — no headroom loss in a warm enclosure until you cross 60 °C, which covers most ventilated panels. Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep, with IP40 protection on the front face — fits standard panel cutouts for 3-pole MCCBs in this frame class, and the IP40 front keeps tools and fingers out during operation.

MPN
3VM1196-5ED32-0AA0