Skip to main content
Siemens 3VM1220-4EE46-0AA2 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VM1220-4EE46-0AA2 MCCB, 200 A, 121 kA at 24

MPN3VM1220-4EE46-0AA2

Siemens SENTRON molded case circuit breaker, 3VM1220-4EE46-0AA2, 4-pole, 200 A rated continuous current, TM220 thermal-magnetic release, LI protection, switching capacity class S, 121 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VM1220-4EE46-0AA2 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VM1220-4EE46-0AA2 — Ratings
ParameterValue
Number of poles4
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V53 kA
Breaking capacity at 500 V17 kA
Power loss, max.42 W

Protection & Trip Unit

3VM1220-4EE46-0AA2 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220

Construction & Connection

3VM1220-4EE46-0AA2 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40

Accessories & Functions

3VM1220-4EE46-0AA2 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VM1220-4EE46-0AA2 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Product details

MCCB with 121 kA interrupting capacity at 240 V

The Siemens SENTRON 3VM1220-4EE46-0AA2 is a 4-pole molded case circuit breaker rated for 200 A continuous current at 40 °C, with a TM220 thermal-magnetic release providing LI (long-time and instantaneous) protection. Its headline interrupting rating is 121 kA at 240 V AC — that is the fault level it can safely clear without welding contacts or venting arc gas into the panel. At 415 V it still holds 76 kA, and at 500 V it drops to 17 kA, so the voltage on your bus determines how much fault current this breaker can handle. The frame is sized for up to 250 A maximum, meaning you can swap the trip unit later if the load grows within that limit.

Thermal derating and panel fit

The breaker holds its full 200 A rating up to 50 °C ambient; above that it derates linearly to 176 A at 70 °C. If this breaker sits in a hot enclosure near other heat sources, use the 55 °C row (194 A) or 60 °C row (188 A) for your continuous load calculation. Front connection via box terminals, IP40 on the front — standard for a panelboard or enclosed switchboard installation. No auxiliary contacts come fitted (0 CO contacts), so if you need remote status signaling, plan a separate auxiliary switch block.

Frequently asked questions

What is the interrupting rating of 3VM1220-4EE46-0AA2 at 240 V?

121 kA at 240 V AC, 76 kA at 415 V, 53 kA at 440 V, and 17 kA at 500 V.

Where can I buy 3VM1220-4EE46-0AA2?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What does the TM220 release designation mean?

TM220 indicates a thermal-magnetic release with LI (long-time and instantaneous) protection characteristics, adjustable for coordination with downstream breakers.

MPN