SENTRON 3VM1220-5MH32-0AA0 — 200 A MCCB with TM120M Release
It carries an interrupting capacity of 187 kA at 240 V AC, 121 kA at 415 V, 76 kA at 440 V, and 30 kA at 500 V — giving you headroom for high-fault installations without cascading upstream gear.
The breaker holds a full 200 A up to 50 °C ambient, then derates linearly: 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. Front protection is IP40 — fine for a clean panel interior, but not for washdown. Dimensions are 105 mm wide × 158 mm high × 70 mm deep, fitting standard 3-pole MCCB panel cutouts.