Skip to main content
Siemens 3VM9154-0JA11 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM9154-0JA11 Box Terminal, 1.5–70 mm², for 3VM 100/

MPN3VM9154-0JA11
Active

Siemens SENTRON, accessories, box terminal TS1.1, 4 units, 1.5…70 mm², for 3VM 100/160, solid 1.5–16 mm²: 45 lb-in, stranded 14–6 AWG: 45 lb-in, 4 AWG–3/0: 70 lb-in.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM9154-0JA11 — Identification
ParameterValue
Product designationaccessories
Brand / rangeSENTRON
3VM9154-0JA11 — Other specifications
ParameterValue
Solid1.5 - 16 mm²: 45 lb-in
Stranded14 - 6 AWG: 45 lb-in 4 AWG - 3/0: 70 lb-in
AccessoriesBox terminal
Finely stranded14 - 6 AWG: 45 lb-in 4 AWG - 3/0: 70 lb-in
Stripped length0.5 in
Designation (Of the terminal)TS1.1
For copper cable (Solid, maximum)10 AWG
For copper cable (Solid, minimum)14 AWG
For copper cable (Stranded, maximum)3/0 AWG
For copper cable (Stranded, minimum)14 AWG
For copper cable (Finely stranded, maximum)3/0 AWG
For copper cable (Finely stranded, minimum)14 AWG

Product details

Terminal specs and wire-range coverage

The 3VM9154-0JA11: The maximum conductor cross-section for finely stranded wire is also 3/0 AWG, so the same torque table applies regardless of stranding class. Minimum solid is 14 AWG; minimum stranded and finely stranded both start at 14 AWG. This range covers typical branch-circuit and feeder terminations on 100 A and 160 A frame breakers.

The product status is listed as Active, meaning Siemens continues to manufacture and support this terminal set as a standard catalog item. No end-of-life notification or last-time-buy window is in effect.

These box terminals mount directly onto the line and load lugs of 3VM 100/160 breakers. They replace the standard screw-clamp terminals when a box-type termination is preferred for larger conductors or higher pullout resistance. The 0.5 in strip length is consistent across all wire sizes, so the wire preparation step is uniform regardless of the gauge being terminated.

Frequently asked questions

What wire sizes and torque values does this terminal accept?

Solid copper: 1.5–16 mm² at 45 lb-in. Stranded and finely stranded: 14–6 AWG at 45 lb-in, 4 AWG–3/0 at 70 lb-in. Stripped length is 0.5 in for all types.

Where can I buy 3VM9154-0JA11 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Does 3VM9154-0JA11 fit 3VM breakers other than 100/160?

The manufacturer specifies this box terminal set for 3VM 100/160 frames only. It is not listed for other frame sizes.

MPN
3VM9154-0JA11