Siemens 3VM9403-0JJ23 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM9403-0JJ23 SENTRON Wire Connector, 600 kcmil

MPN3VM9403-0JJ23
Active

Siemens SENTRON TA2.4 circular conductor terminal, 3VM9403-0JJ23, for 3VM 400/630 A breakers, 2/0–600 kcmil Cu/Al, 450 lb-in torque, stripped length 1.2/2.3 in.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VM9403-0JJ23 — Identification
ParameterValue
Product designationaccessories
Brand / rangeSENTRON

Other specifications

3VM9403-0JJ23 — Other specifications
ParameterValue
Stranded450 lb-in
AccessoriesWire connector
Finely stranded450 lb-in
Stripped length1.2 / 2.3 in
Design of the productcircular conductor terminal
Designation (Of the terminal)TA2.4
For copper cable (Stranded, maximum)600 kcmil
For copper cable (Stranded, minimum)2/0 AWG
For aluminum cable (Stranded, maximum)600 kcmil
For aluminum cable (Stranded, minimum)2/0 AWG
For copper cable (Finely stranded, maximum)600 kcmil
For copper cable (Finely stranded, minimum)2/0 AWG
Type of electrical connection (With control wire tap)No

Product details

What it is and what it fits

The 3VM9403-0JJ23 is a SENTRON TA2.4 circular conductor terminal — a wire connector designed as an accessory for Siemens 3VM molded-case circuit breakers in the 400 A and 630 A frame sizes. It handles two cables per terminal, each 70–300 mm², and accepts copper or aluminum conductors from 2/0 AWG up to 600 kcmil — covering the full range of feeder and distribution cable sizes you'd land on a 400–630 A breaker. Stripped length is 1.2 in for the smaller cable range and 2.3 in for the larger — that's the bare conductor length you need before insertion.

Integration note

This is a lug-style terminal that bolts onto the breaker's line or load side — no DIN-rail mounting, no panel cutout. The 3VM breaker itself snaps onto a mounting plate or DIN rail; the terminal is an add-on for cable termination. No control-wire tap on this version — it's a straight power connector. If you need a tap for auxiliary wiring, that's a different TA variant.

Frequently asked questions

What cable sizes does 3VM9403-0JJ23 accept?

It accepts copper or aluminum stranded cable from 2/0 AWG minimum up to 600 kcmil maximum, and finely stranded copper in the same range. Each terminal takes two cables 70–300 mm².

MPN
3VM9403-0JJ23