4EM5005-6CB00 — Inductance & Impedance
ParameterValue
Rated inductance0.0027H
Relative inductive voltage drop4%
4EM5005-6CB00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EM5005-6CB00 — Electrical
ParameterValue
Rated operating voltage400V
Rated current (AC)16.2A
Number of phases1
Current (AC), max.18A
Rated current (DC)22A
Voltage typeAC
Rated operating frequency50Hz
4EM5005-6CB00 — Losses & Thermal
ParameterValue
Power loss, coil (W)18W
Power loss, iron core (W)19.7W
Rated ambient temperature40°C
4EM5005-6CB00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EM5005-6CB00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals / tab terminals
IP protection ratingIP00
Height0.111m
Width0.097m
Depth0.115m

Product details

The Siemens 4EM5005-6CB00 is a single-phase commutating choke (line reactor) designed for converter applications. It limits current rise and reduces harmonic distortion on the AC line feeding a variable-frequency drive or DC drive. Rated for 400 V AC at 50 Hz, it carries 18 A maximum AC current (16.2 A rated operational current) and 22 A DC rated current. The 2.7 mH inductance and 4% relative inductive voltage drop are sized for typical drive input circuits.

IP00 means it's an open-frame component — no enclosure protection. Mount it inside a cabinet where it's protected from dust and moisture. Dimensions are 0.115 m deep, 0.097 m wide, 0.111 m high. Connections are screw-type or tab terminals, so it integrates into a standard control panel with ring or fork lugs. The thermal class B (130 °C) insulation system per IEC 60085 means it handles the heat from 18 W coil loss and 19.7 W iron core loss without derating up to 40 °C ambient.

Frequently asked questions

Where can I buy 4EM5005-6CB00 and how do I get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What are the key electrical ratings of 4EM5005-6CB00?

Rated 400 V AC, 50 Hz, 18 A AC maximum (16.2 A rated operational), 22 A DC rated, 2.7 mH inductance, 4% inductive voltage drop.

What is the physical size of 4EM5005-6CB00?

Depth 0.115 m, width 0.097 m, height 0.111 m.

MPN
4EM5005-6CB00