Siemens 4EM5115-0EB00 — Line/Load Reactors

Siemens 4EM5115-0EB00 Commutating Choke, 22.5 A, 460 V

MPN4EM5115-0EB00

Siemens 4EM5115-0EB00, single-phase commutating choke for converters, rated 22.5 A / 460 V AC, 60 Hz, IP00, screw terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EM5115-0EB00 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitscrew-type terminals
Operating voltage rated value460V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Power loss [W] of the coil13.3W
Power loss [W] of the iron core33.7W
Operating frequency rated value60Hz
Phase number1
Ambient temperature rated value40°C
Depth0.129m
Width0.097m
Height0.111m
Thermal class acc. to IEC 60085B
Rated value22.5A
At DC rated value30.6A
Protection class IPIP00
Inductivity rated value0.002H

Product details

The Siemens 4EM5115-0EB00 is a single-phase commutating choke (line reactor) for converter applications. It limits current rise and reduces harmonics on the input side of a variable-frequency drive or DC drive — the inductive drop of 4% at rated current is the design target, matching typical line-reactor sizing for drive input circuits.

Rated 22.5 A continuous at 460 V AC, 60 Hz, with a maximum current of 25 A — the 22.5 A figure is the thermal current (Ith) for continuous duty; the 25 A maximum is the short-term overload ceiling. For DC-side applications the same choke carries 30.6 A DC, which is useful if you are using it on the DC link of a converter rather than the AC input. Inductance is 0.002 H at rated conditions. Total power loss splits between the coil (13.3 W) and the iron core (33.7 W), summing to 47 W at full load. Thermal class B (130 °C) insulation per IEC 60085 means the winding can operate at up to 130 °C hot-spot temperature without accelerated aging — adequate for most industrial enclosures at 40 °C ambient.

IP00 — no enclosure protection. Dimensions are 0.097 m wide by 0.111 m tall by 0.129 m deep.

Frequently asked questions

What are the key ratings of the 4EM5115-0EB00?

Rated 22.5 A continuous at 460 V AC, 60 Hz, with a maximum of 25 A. Inductance is 0.002 H with a 4% inductive voltage drop. For DC use it carries 30.6 A. Thermal class B insulation, IP00, screw terminals.

MPN
4EM5115-0EB00