Siemens 4EM5115-0EB00 — Line/Load Reactors

Siemens 4EM5115-0EB00 Commutating Choke, 22.5 A, 460 V

MPN4EM5115-0EB00

Siemens 4EM5115-0EB00, single-phase commutating choke for converters, rated 22.5 A / 460 V AC, 60 Hz, IP00, screw terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EM5115-0EB00 — Inductance & Impedance
ParameterValue
Rated inductance0.002H
Relative inductive voltage drop4%

Identification

4EM5115-0EB00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EM5115-0EB00 — Electrical
ParameterValue
Rated operating voltage460V
Number of phases1
Rated current (DC)30.6A
Voltage typeAC
Rated operating frequency60Hz

Losses & Thermal

4EM5115-0EB00 — Losses & Thermal
ParameterValue
Power loss, coil (W)13.3W
Power loss, iron core (W)33.7W
Rated ambient temperature40°C

Approvals

4EM5115-0EB00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EM5115-0EB00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.111m
Width0.097m
Depth0.129m

Product details

What it is and what it does

The Siemens 4EM5115-0EB00 is a single-phase commutating choke (line reactor) for converter applications. It limits current rise and reduces harmonics on the input side of a variable-frequency drive or DC drive — the inductive drop of 4% at rated current is the design target, matching typical line-reactor sizing for drive input circuits.

Key ratings and what they mean for fit

Rated 22.5 A continuous at 460 V AC, 60 Hz, with a maximum current of 25 A — the 22.5 A figure is the thermal current (Ith) for continuous duty; the 25 A maximum is the short-term overload ceiling. For DC-side applications the same choke carries 30.6 A DC, which is useful if you are using it on the DC link of a converter rather than the AC input. Inductance is 0.002 H at rated conditions. The 4% relative inductive voltage drop at rated current is the design target. Total power loss splits between the coil (13.3 W) and the iron core (33.7 W), summing to 47 W at full load. Thermal class B (130 °C) insulation per IEC 60085 means the winding can operate at up to 130 °C hot-spot temperature without accelerated aging — adequate for most industrial enclosures at 40 °C ambient.

Mounting and integration

IP00 — no enclosure protection. Dimensions are 0.097 m wide by 0.111 m tall by 0.129 m deep.

Frequently asked questions

What are the key ratings of the 4EM5115-0EB00?

Rated 22.5 A continuous at 460 V AC, 60 Hz, with a maximum of 25 A. Inductance is 0.002 H with a 4% inductive voltage drop. For DC use it carries 30.6 A. Thermal class B insulation, IP00, screw terminals.

MPN
4EM5115-0EB00