Skip to main content
Siemens 4EM5200-0AK00 — Line/Load Reactors

Siemens 4EM5200-0AK00 Commutating Choke, 90A Max, 230V AC

MPN4EM5200-0AK00

Siemens 4EM5200-0AK00, 1-phase commutating choke for converters, 230V AC, 90A max / 81A rated, 0.2 mH, IP00, screw terminals, EN 61558-2-20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EM5200-0AK00 — Inductance & Impedance
ParameterValue
Rated inductance0.0002H
Relative inductive voltage drop1.91%
4EM5200-0AK00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EM5200-0AK00 — Electrical
ParameterValue
Rated operating voltage230V
Number of phases1
Rated current (DC)110.2A
Voltage typeAC
Rated operating frequency50Hz
4EM5200-0AK00 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EM5200-0AK00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EM5200-0AK00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.109m
Width0.121m
Depth0.149m

Product details

The Siemens 4EM5200-0AK00 is a 1-phase commutating choke designed for converter applications. It carries a maximum current of 90 A and a rated current of 81 A at 230 V AC, 50 Hz — the 81 A figure is the continuous thermal rating under the specified ambient of 40 °C and thermal class B insulation per IEC 60085, so that is the number to use for sustained line-side filtering duty. The 90 A maximum is the short-term overload ceiling, not a steady-state limit. Inductance is 0.0002 H (0.2 mH), with a relative inductive voltage drop of 1.91% at the rated current, voltage, and frequency. That drop figure tells you the choke's impedance at 50 Hz — useful for predicting voltage sag across the component in the converter's DC link or AC input stage.

This is an open-frame (IP00) component — no enclosure, so it must be installed inside a panel or cabinet that provides the environmental protection. Dimensions are 0.149 m depth, 0.121 m width, 0.109 m height. The screw-type terminals accept the main circuit wiring; plan for panel space that accommodates the choke body and clearance for air circulation around the thermal class B winding.

Frequently asked questions

What are the key electrical ratings of the 4EM5200-0AK00?

The choke is rated for 81 A continuous at 230 V AC, 50 Hz, with a maximum current of 90 A. Inductance is 0.2 mH, and the relative inductive voltage drop is 1.91% at rated conditions.

What compliance standard does the 4EM5200-0AK00 meet?

It is designed per EN 61558-2-20, the standard for chokes for converters. Thermal class B insulation per IEC 60085 is specified.

Where can I buy the 4EM5200-0AK00 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm commercial offer.

MPN
4EM5200-0AK00