Siemens 4EM5316-6CB00 — Line/Load Reactors

Siemens 4EM5316-6CB00 Commutating Choke, 45A, 400V, 0.97mH

MPN4EM5316-6CB00

Siemens 4EM5316-6CB00 commutating choke for converter applications, 1-phase, 400V AC, 45A rated, 0.97mH, IP00, screw terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EM5316-6CB00 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitscrew-type terminals
Operating voltage rated value400V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Power loss [W] of the coil28W
Power loss [W] of the iron core52W
Operating frequency rated value50Hz
Phase number1
Ambient temperature rated value40°C
Depth0.139m
Width0.151m
Height0.168m
Thermal class acc. to IEC 60085B
Rated value45A
At DC rated value61.2A
Protection class IPIP00
Inductivity rated value0.00097H

Product details

The Siemens 4EM5316-6CB00 is a single-phase commutating choke (line reactor) designed for converter front-ends. It's rated for 45 A continuous (50 A max) at 400 V AC, 50 Hz, with an inductance of 0.97 mH and a relative inductive voltage drop of 4% at rated current. This is an IP00 component — no enclosure protection — so it's intended for installation inside a panel or cabinet where the environment is controlled. The 0.168 m height, 0.151 m width, and 0.139 m depth footprint needs to be accounted for in the panel layout. Power loss splits between the coil (28 W) and the iron core (52 W), totaling 80 W of heat to dissipate at full load. Thermal class B per IEC 60085 means the insulation system is rated for a 130 °C maximum hot-spot temperature, with a 40 °C ambient rating.

The 4EM5316-6CB00 carries a mature lifecycle status from Siemens — it's an established catalog item, not newly introduced and not flagged for phase-out. Availability is confirmed at time of quote through independent distribution channels. There is no official successor order code listed; the mature status suggests ongoing production support without an imminent last-time-buy window.

Integration Notes

The IP00 rating means no gasket or seal — mount it where the panel's own enclosure provides the environmental protection. Verify your converter's minimum bus voltage requirement against this drop. Single-phase design limits this choke to single-phase converter inputs. For three-phase applications, you'd need three units or a three-phase reactor.

Frequently asked questions

Where can I buy 4EM5316-6CB00?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key electrical ratings for 4EM5316-6CB00?

Rated current 45 A (max 50 A), operating voltage 400 V AC, frequency 50 Hz, inductance 0.97 mH, relative inductive voltage drop 4%.

What is the physical size of 4EM5316-6CB00?

Dimensions are 0.168 m height, 0.151 m width, and 0.139 m depth.

What protection class does 4EM5316-6CB00 have?

IP00 — no ingress protection. It must be installed inside a panel or cabinet that provides the environmental sealing.

MPN
4EM5316-6CB00