Siemens 4EM5316-7CB00 — Line/Load Reactors

Siemens 4EM5316-7CB00 Commutating Choke, 81A, 480V, 0.34mH

MPN4EM5316-7CB00

Siemens 4EM5316-7CB00 commutating choke for converter drives, 1-phase, 480V AC, 81A rated / 90A max, 0.34 mH, 2% voltage drop, IP00, flat-type terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EM5316-7CB00 — Inductance & Impedance
ParameterValue
Rated inductance0.00034H
Relative inductive voltage drop2%

Identification

4EM5316-7CB00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EM5316-7CB00 — Electrical
ParameterValue
Rated operating voltage480V
Number of phases1
Rated current (DC)110.2A
Voltage typeAC
Rated operating frequency50Hz

Losses & Thermal

4EM5316-7CB00 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C

Approvals

4EM5316-7CB00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EM5316-7CB00 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.135m
Width0.151m
Depth0.155m

Product details

What it is and what it does

The Siemens 4EM5316-7CB00 is a 1-phase commutating choke (line reactor) designed for converter drive applications. It limits current rise and harmonics on the AC line side of a variable-frequency drive or DC drive converter, rated for 81 A continuous with a 90 A maximum peak capability at 480 V AC, 50 Hz. The 0.34 mH inductance and 2% relative inductive voltage drop (at rated current, voltage, and frequency) define the impedance it inserts into the circuit — enough to smooth commutation notches and reduce reflected-wave stress on the drive's input rectifier.

Ratings and what they mean for fit

The 81 A rated current (I_LN) is the continuous thermal rating at 40 °C ambient. The 90 A maximum (I_thmax) is the short-term overload ceiling. IP00 means it's an open-frame component — no enclosure, no touch protection. It must be mounted inside a panel or cabinet that provides the required ingress protection and clearance to live parts. The flat-type terminals accept bus-bar or cable-lug connections, not spring-cage or screw-clamp wire terminations.

Where it goes in the panel

Mount this choke on the AC input side of the converter, between the line supply and the drive's rectifier. The 0.155 m depth, 0.151 m width, and 0.135 m height define the footprint — verify clearance for the flat-type terminals and air flow for natural convection cooling. No DIN-rail clip; it's a bolt-down component.

Frequently asked questions

Will the 4EM5316-7CB00 drop into a panel designed for a 5SJ3140-7 circuit breaker?

No — the 5SJ3140-7 is a 1-pole miniature circuit breaker (MCB) with a 40 A rating, DIN-rail mount, and IP20 enclosure. The 4EM5316-7CB00 is a bolt-down commutating choke rated for 81 A with flat-type terminals and IP00 open-frame construction. They serve completely different functions and mounting methods; no direct substitution is possible.

MPN
4EM5316-7CB00