Skip to main content
Siemens 4EP3200-4US00 — Line/Load Reactors

Siemens 4EP3200-4US00 Mains Choke, 3-Phase, 1.5 A, 9.4 mH

MPN4EP3200-4US00
Active

Siemens 4EP3200-4US00 mains choke for VFD, 3-phase AC, 400/480 V, 1.5 A max, 9.4 mH, IP00, screw/tab terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EP3200-4US00 — Inductance & Impedance
ParameterValue
Rated inductance0.0094H
Relative inductive voltage drop2%
4EP3200-4US00 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EP3200-4US00 — Electrical
ParameterValue
Rated operating voltage400, 480V
Rated current (AC)1.35A
Number of phases3
Current (AC), max.1.5A
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EP3200-4US00 — Losses & Thermal
ParameterValue
Power loss, coil (W)16.7W
Power loss, iron core (W)4.5W
Rated ambient temperature40°C
4EP3200-4US00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EP3200-4US00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals / tab terminals
IP protection ratingIP00
Height0.108m
Width0.088m
Depth0.057m

Product details

The Siemens 4EP3200-4US00 is a three-phase mains choke (line reactor) designed for variable-frequency drive input circuits. It carries a rated operating voltage of 400/480 V AC at 50/60 Hz and a maximum continuous current of 1.5 A, with a rated current of 1.35 A. This is an open-frame (IP00) component, so it must be mounted inside an enclosure that provides physical protection and clearance for airflow. The total power loss splits into 16.7 W in the coil and 4.5 W in the iron core at rated load and 40 °C ambient — factor that into your enclosure thermal budget. Thermal class B per IEC 60085 means the insulation system is rated for a 130 °C hot-spot temperature, which is standard for this class of reactor and leaves headroom for moderate overloads.

The 4EP3200-4US00 measures 0.088 m wide by 0.108 m tall by 0.057 m deep. It is not a DIN-rail snap-on device — the screw-type and tab terminals indicate it is intended for panel-mount or chassis-mount with wiring lugs. Plan for a dedicated mounting plate and leave clearance around the IP00 core for convection cooling.

Frequently asked questions

How do I get current pricing and availability for 4EP3200-4US00?

Submit an RFQ through this listing. We source this part through independent distribution and confirm price and lead time at quote time.

What compliance documentation does the brand provide for 4EP3200-4US00?

The part is recognized under UL/CSA and designed to EN 61558-2-20. RoHS and REACH declarations are typically available from the manufacturer upon request.

What are the key electrical ratings of 4EP3200-4US00?

Rated voltage 400/480 V AC, 50/60 Hz, three-phase. Maximum continuous current 1.5 A, rated current 1.35 A. Inductance 9.4 mH, voltage drop 2% at rated conditions. Total power loss 21.2 W (coil + iron) at 40 °C ambient.

MPN
4EP3200-4US00