Skip to main content
Siemens 4EP3400-1US00 — Line/Load Reactors

Siemens 4EP3400-1US00 Mains Choke for VFD, 11.2A, 480V

MPN4EP3400-1US00
Active

Siemens 4EP3400-1US00 mains choke for VFD, 3-phase, AC, 480V, 11.2A max, 1.3 mH, IP00, screw/tab terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EP3400-1US00 — Inductance & Impedance
ParameterValue
Rated inductance0.0013H
Relative inductive voltage drop2%
4EP3400-1US00 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EP3400-1US00 — Electrical
ParameterValue
Rated operating voltage400, 480V
Rated current (AC)10.08A
Number of phases3
Current (AC), max.11.2A
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EP3400-1US00 — Losses & Thermal
ParameterValue
Power loss, coil (W)23W
Power loss, iron core (W)11W
Rated ambient temperature40°C
4EP3400-1US00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EP3400-1US00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals / tab terminals
IP protection ratingIP00
Height0.122m
Width0.124m
Depth0.073m

Product details

Mains choke for VFD — 3-phase, 480V, 11.2A

The Siemens 4EP3400-1US00 is a 3-phase mains choke (Netzdrossel f. FU) designed for variable-frequency drive input line conditioning. It handles a maximum AC current of 11.2 A at 480 V, with a rated operational current of 10.08 A, and provides 1.3 mH inductance per phase. Rated for 50/60 Hz operation at 40°C ambient, this choke dissipates 23 W in the coil and 11 W in the iron core, with Class B insulation (130°C rise) per IEC 60085. Connection is via screw-type or tab terminals on the main circuit.

Panel integration

At 0.124 m wide, 0.122 m tall, and 0.073 m deep, this choke fits a standard backpanel footprint. The IP00 rating requires enclosure mounting — plan for a gland plate or terminal box to maintain the panel's overall IP rating. Screw/tab terminals accept ring or fork lugs; torque to the manufacturer's specification for the connection type used.

Frequently asked questions

What compliance documentation does the 4EP3400-1US00 carry?

The choke is designed to EN 61558-2-20 and is UL/CSA recognized, covering North American and IEC installation requirements for drive input chokes.

Where can I buy the 4EP3400-1US00 and how is it quoted?

The 4EP3400-1US00 is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN
4EP3400-1US00