Skip to main content
Siemens 4EP3500-0GK00 — Line/Load Reactors

Siemens 4EP3500-0GK00 Mains Choke, 6.3A 400V AC, 4.2mH

MPN4EP3500-0GK00

Siemens 4EP3500-0GK00 mains choke (Netzdrossel f. FU), 3-phase, 400V AC, 6.3A rated, 4.2mH, 4% voltage drop, IP00, screw/tab terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EP3500-0GK00 — Inductance & Impedance
ParameterValue
Rated inductance0.0042H
Relative inductive voltage drop4%
4EP3500-0GK00 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EP3500-0GK00 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EP3500-0GK00 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EP3500-0GK00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EP3500-0GK00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals / tab terminals
IP protection ratingIP00
Height0.139m
Width0.148m
Depth0.068m
4EP3500-0GK00 — Other specifications
ParameterValue
Rated value6.3A

Product details

The Siemens 4EP3500-0GK00 is a three-phase mains choke — a line reactor — designed for the input side of a variable-frequency drive (VFD). It smooths line current, reduces harmonic distortion, and limits inrush current spikes that would otherwise stress the drive's DC bus capacitors. The rated inductance of 4.2 mH (0.0042 H) at 400 V AC, 50 Hz, with a 4 % relative inductive voltage drop, means it presents a predictable impedance to the line, damping harmonics across the switching frequency range. The rated current of 6.3 A (maximum 7 A) sets the continuous load it can carry at 40 °C ambient; thermal class B (130 °C insulation rating) per IEC 60085 limits the winding temperature rise. IP00 means it is an open, chassis-mount component — no enclosure, so it must be installed inside a panel with adequate clearance and ventilation.

The choke measures 148 mm wide, 139 mm high, and 68 mm deep — a compact footprint for a 6.3 A three-phase reactor. It uses screw-type terminals and tab terminals for the main current connections, which accept standard ring or fork lugs. The thermal class B (130 °C) winding insulation means the surface temperature can reach 100 °C under full load; allow for natural convection airflow around the choke and avoid mounting directly above heat-sensitive components.

Frequently asked questions

Where can I buy 4EP3500-0GK00 and how do I get a price?

This part is sourced to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ and we will respond with a firm price and lead time.

What is 4EP3500-0GK00's listed depth (0.068m) on this component line?

The depth is 0.068 m (68 mm). That is the front-to-back dimension when mounted on a panel or chassis.

What is 4EP3500-0GK00's listed width (0.148m) on this component line?

The width is 0.148 m (148 mm). That is the horizontal dimension across the mounting base.

MPN
4EP3500-0GK00