Skip to main content
Siemens 4EP3600-3DS00 — Line/Load Reactors

Siemens 4EP3600-3DS00 Commutating Choke, 400V 3-Phase 25.2A

MPN4EP3600-3DS00

Siemens 4EP3600-3DS00, commutating choke for converter, 3-phase, 400V AC, 25.2A rated, 28A max, 0.5mH, IP00, screw terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EP3600-3DS00 — Inductance & Impedance
ParameterValue
Rated inductance0.0005H
Relative inductive voltage drop2%
4EP3600-3DS00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EP3600-3DS00 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Rated current (DC)34.3A
Voltage typeAC
Rated operating frequency50Hz
4EP3600-3DS00 — Losses & Thermal
ParameterValue
Power loss, coil (W)39W
Power loss, iron core (W)8.7W
Rated ambient temperature40°C
4EP3600-3DS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EP3600-3DS00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.139m
Width0.148m
Depth0.078m

Product details

The Siemens 4EP3600-3DS00 is a 3-phase commutating choke for line-commutated converters — the inductive element that limits di/dt and smooths the DC link ripple in a 400 V AC drive or rectifier circuit. Rated 25.2 A continuous (28 A max) with 0.5 mH inductance and a 2 % relative inductive voltage drop at rated current, it is sized for the input side of a 3-phase converter feeding a motor drive or DC bus. The IP00 open-frame construction means it mounts inside a panel or enclosure that provides its own touch protection — this is not a stand-alone outdoor part.

The 25.2 A rated current (28 A maximum) at 400 V AC, 50 Hz, is the thermal continuous rating at 40 °C ambient with thermal class B insulation (130 °C hot-spot). That 25.2 A figure governs the converter input current it can handle without saturating or overheating — size the upstream line reactor or transformer for that continuous load, not the peak. The 0.5 mH inductance and 2 % relative inductive drop are matched to the commutation requirements of a 6-pulse or 12-pulse thyristor bridge; a choke with significantly different inductance changes the overlap angle and may increase notching or reduce the available DC voltage. Power loss splits between 39 W in the coil and 8.7 W in the iron core at rated load — total 47.7 W of heat to vent inside the panel.

Termination and integration notes

The 0.078 m depth, 0.148 m width, and 0.139 m height define the mounting footprint; allow clearance for air flow and terminal access. IP00 means no integral finger protection — the panel builder must provide the enclosure and any required touch-safe shrouding. Thermal class B insulation (130 °C) gives headroom above the 40 °C ambient rating, but the 47.7 W total loss must be vented; do not bury the choke in a sealed compartment without forced air or a thermal calculation.

Frequently asked questions

Where can I buy 4EP3600-3DS00 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What are the key specifications of 4EP3600-3DS00?

3-phase commutating choke for converters, 400 V AC, 50 Hz, 25.2 A rated current (28 A max), 0.5 mH inductance, 2 % relative inductive drop, IP00, screw terminals, thermal class B.

Does 4EP3600-3DS00 have a direct replacement or second-source?

No official Siemens successor or direct cross-reference is listed. The peers in evidence (5SJ3140-7, 5SL6606-7YA, 3RV1011-0GA10) are circuit breakers, not chokes — they are not functional substitutes for a commutating choke.

MPN