Skip to main content
Siemens 4EP3600-3US00 — Line/Load Reactors

Siemens 4EP3600-3US00 Mains Choke, 22.4 A, 0.82 mH, 500 V AC

MPN4EP3600-3US00
Active

Siemens SENTRON 4EP3600-3US00 mains choke for frequency converters, 3-phase, 500 V AC, 22.4 A, 0.82 mH, 50 Hz, IP00, screw terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EP3600-3US00 — Inductance & Impedance
ParameterValue
Rated inductance0.00082H
Relative inductive voltage drop2%
4EP3600-3US00 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EP3600-3US00 — Electrical
ParameterValue
Rated operating voltage500V
Rated current (AC)20.16A
Number of phases3
Current (AC), max.22.4A
Voltage typeAC
Rated operating frequency50Hz
4EP3600-3US00 — Losses & Thermal
ParameterValue
Power loss, coil (W)49.6W
Power loss, iron core (W)3.8W
Rated ambient temperature40°C
4EP3600-3US00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EP3600-3US00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.139m
Width0.148m
Depth0.078m

Product details

The Siemens 4EP3600-3US00 is a three-phase mains choke (line reactor) designed for use with frequency converters — the German product designation "Netzdrossel f. FU" tells you exactly that. It's rated for 22.4 A maximum continuous current at 500 V AC, 50 Hz, with an inductance of 0.82 mH and a relative inductive voltage drop of 2% at rated conditions. That 2% drop is typical for a line reactor sized to smooth incoming power and limit harmonic distortion and peak currents on the drive's input side. The 22.4 A rating is the thermal maximum (Ithmax) — the continuous current it can carry at 40 °C ambient without exceeding the Class B temperature rise limit per IEC 60085. The slightly lower 20.16 A operational current (I LN) reflects the nominal load point under rated voltage and frequency. Total power loss splits between 49.6 W in the coil and 3.8 W in the iron core, which matters for enclosure heat buildup.

Dimensions are 0.148 m wide by 0.139 m tall by 0.078 m deep, with screw-type terminals for the main circuit connections. Plan for adequate clearance around the choke for airflow; the 49.6 W coil loss needs ventilation to stay within the 40 °C ambient rating.

Frequently asked questions

What compliance documentation does the 4EP3600-3US00 carry?

The part is UL/CSA-recognized and built to EN 61558-2-20, which covers reactors and chokes. It also carries the CE mark as a Siemens industrial product.

Where can I buy 4EP3600-3US00 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Submit a request for current pricing and availability — quantities and lead times are confirmed at quote time.

What are the key ratings for 4EP3600-3US00?

Rated 22.4 A maximum continuous current at 500 V AC, 50 Hz, with 0.82 mH inductance and a 2% voltage drop at rated load. Operational current is 20.16 A. Ambient rating is 40 °C with Class B insulation.

MPN
4EP3600-3US00