Skip to main content
Siemens 4EP3600-5DS00 — Line/Load Reactors

Siemens 4EP3600-5DS00 Commutating Choke, 3-Phase 400V 35.5A

MPN4EP3600-5DS00

Siemens 4EP3600-5DS00 commutating choke for converter, 3-phase, 400V AC, 35.5A max / 31.95A rated, 0.4 mH, IP00, screw-type terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP3600-5DS00 — Inductance & Impedance
ParameterValue
Rated inductance0.0004H
Relative inductive voltage drop2%

Identification

4EP3600-5DS00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EP3600-5DS00 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Rated current (DC)43.5A
Voltage typeAC
Rated operating frequency50Hz

Losses & Thermal

4EP3600-5DS00 — Losses & Thermal
ParameterValue
Power loss, coil (W)39W
Power loss, iron core (W)9W
Rated ambient temperature40°C

Approvals

4EP3600-5DS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP3600-5DS00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.139m
Width0.148m
Depth0.078m

Product details

What it is and what it does

The Siemens 4EP3600-5DS00 is a commutating choke (line reactor) designed for converter applications, smoothing current ripple and limiting di/dt on the AC line side of drives and rectifiers. It is a 3-phase, 400 V AC rated choke with a maximum continuous current of 35.5 A and a rated current of 31.95 A at 50 Hz. The 0.4 mH inductance and 2% relative inductive voltage drop define its filtering characteristic — sized to protect the converter's input bridge from excessive current rise without dropping too much voltage under load.

Key ratings — what they mean for fit

The 35.5 A maximum (Ithmax) is the thermal limit at 40 °C ambient — the choke can carry this current continuously without exceeding Class B (130 °C) insulation rise. The 31.95 A rated current (ILN) is the design point for the 2% voltage drop; at this current the choke drops about 8 V line-to-line, which the drive's DC bus regulation typically absorbs. The DC rated value of 43.5 A applies when the choke is used in a DC link circuit — a different duty than the AC line side. The IP00 protection class means the choke is open-frame: it must be mounted inside a panel or enclosure that provides the environmental seal. Screw-type terminals accept standard power wiring.

Where it is used

This choke sits between the AC mains and the input of a variable-frequency drive, DC drive, or regenerative converter. It reduces harmonic distortion, limits inrush current, and protects the converter's diodes or IGBTs from commutation notches. In cold-chain or refrigeration applications — where ammonia or CO2 compressors run on VFDs — the choke helps maintain power quality and extends drive life in electrically noisy environments. The open-frame design (IP00) requires panel mounting; the 148 mm width, 139 mm height, and 78 mm depth fit a standard subpanel footprint.

Frequently asked questions

How do I get current pricing and availability for 4EP3600-5DS00?

Submit an RFQ against this order code. The part is sourced through independent distribution; availability and current pricing are confirmed at quote time — no stock or price figures are published here.

What are the key ratings of 4EP3600-5DS00?

3-phase commutating choke, 400 V AC, 50 Hz, 35.5 A max continuous, 31.95 A rated, 0.4 mH inductance, 2% voltage drop, IP00 enclosure, screw terminals, Class B insulation (130 °C).

MPN
4EP3600-5DS00