Skip to main content
Siemens 4EP3601-0DS00 — Line/Load Reactors

Siemens 4EP3601-0DS00 Commutating Choke, 18A, 400V AC, 1.4mH

MPN4EP3601-0DS00

Siemens 4EP3601-0DS00 commutating choke for converter, 3-phase, 400V AC, 18A rated, 1.4mH, IP00, screw-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EP3601-0DS00 — Inductance & Impedance
ParameterValue
Rated inductance0.0014H
Relative inductive voltage drop4%
4EP3601-0DS00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EP3601-0DS00 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Rated current (DC)24.5A
Voltage typeAC
Rated operating frequency50Hz
4EP3601-0DS00 — Losses & Thermal
ParameterValue
Power loss, coil (W)39W
Power loss, iron core (W)9.3W
Rated ambient temperature40°C
4EP3601-0DS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EP3601-0DS00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.126m
Width0.148m
Depth0.078m

Product details

The Siemens 4EP3601-0DS00 is a 3-phase commutating choke for converter applications, designed to limit current rise and reduce harmonic distortion on the DC link of a variable-speed drive or inverter. It is rated for 400 V AC at 50 Hz, with a rated inductance of 1.4 mH and a relative inductive voltage drop of 4% at the measurement level — meaning it introduces a predictable impedance that smooths commutation notches and protects the converter's semiconductor switches from excessive di/dt. The choke carries a thermal continuous current (Ith) of 20 A and a rated current (I LN) of 18 A, with a DC-rated current of 24.5 A. This makes it suitable for line-side or load-side filtering in a 400 V class drive system where the continuous motor current stays at or below 18 A AC.

The 1.4 mH inductance at 50 Hz, combined with the 4% voltage drop, gives a predictable impedance that helps meet EMC requirements by limiting high-frequency current ripple. The power loss splits into 39 W in the coil and 9.3 W in the iron core, for a total of 48.3 W at rated conditions — heat that must be accounted for in the enclosure thermal budget. Thermal class B (130 °C) insulation per IEC 60085 means the winding can operate continuously at up to 130 °C hot-spot temperature, with a 40 °C ambient rating. The 3-phase design matches standard 400 V AC drives; the DC current rating of 24.5 A gives headroom if the choke is used on the DC bus rather than the AC line.

Frequently asked questions

How do I get current pricing and availability for 4EP3601-0DS00?

Submit an RFQ through the storefront. Availability and current pricing are confirmed at quote time through the independent distribution channel — no stock figures or price lists are published here.

What are the key electrical ratings of 4EP3601-0DS00?

Rated voltage 400 V AC, 50 Hz; rated current 18 A; thermal maximum current 20 A; DC rated current 24.5 A; inductance 1.4 mH; voltage drop 4%; total power loss 48.3 W.

What is the protection class and connection type?

IP00 open-frame construction, intended for panel or enclosure mounting. Main circuit connections are screw-type terminals.

MPN
4EP3601-0DS00