Siemens 4EP3602-0DS00 — Line/Load Reactors

Siemens 4EP3602-0DS00 Commutating Choke, 3-Phase, 16.2A, 500

MPN4EP3602-0DS00

Siemens SENTRON 4EP3602-0DS00 commutating choke for converters, 3-phase, 16.2 A rated current, 500 V AC, 1.6 mH, IP00, screw-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EP3602-0DS00 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitscrew-type terminals
Operating voltage rated value500V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Peak current23A
Power loss [W] of the coil37W
Power loss [W] of the iron core7.1W
Operating frequency rated value50Hz
Phase number3
Ambient temperature rated value40°C
Depth0.078m
Width0.148m
Height0.126m
Thermal class acc. to IEC 60085B
Rated value16.2A
At DC rated value22A
Protection class IPIP00
Inductivity rated value0.0016H

Product details

Commutating choke for converter duty

The Siemens 4EP3602-0DS00 is a three-phase commutating choke (line reactor) designed for converter input circuits. It carries a rated current of 16.2 A, with a maximum continuous current of 18 A and a peak current capability of 23 A, at a rated operating voltage of 500 V AC and 50 Hz. The 1.6 mH inductance limits the rate of current rise during converter commutation, reducing harmonic distortion and protecting the rectifier diodes. This is the choke that goes between the line supply and the converter's input — not a motor-side output reactor.

The 16.2 A rated current (I_LN) sets the continuous load the choke can carry at 40 °C ambient. The 4 % relative inductive voltage drop (uk) at rated current and frequency tells you the voltage the choke will drop at full load — critical for sizing the DC bus voltage margin in the drive. The thermal class B winding (130 °C) and the combined coil plus iron-core loss of about 44 W (37 W coil + 7.1 W iron) mean the choke will run warm; allow free air circulation or forced ventilation in the enclosure.

Frequently asked questions

Where can I buy the 4EP3602-0DS00 and get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — stock and lead time are confirmed at the time of quote.

What is the depth of the 4EP3602-0DS00?

The listed depth is 0.078 m (78 mm).

What is the width of the 4EP3602-0DS00?

The listed width is 0.148 m (148 mm).

What compliance documentation does Siemens provide for the 4EP3602-0DS00?

The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this order code. The choke is designed to EN 61558-2-20. For detailed compliance certificates, include the request with your RFQ.