Skip to main content
Siemens 4EP3603-6DS00 — Line/Load Reactors

Siemens 4EP3603-6DS00 Commutating Choke, 3-Phase, 12A, 1.6 m

MPN4EP3603-6DS00

Siemens 4EP3603-6DS00 commutating choke for converter, 3-phase AC, 12 A rated current, 1.6 mH, IP00, screw/tab terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP3603-6DS00 — Inductance & Impedance
ParameterValue
Rated inductance0.0016H
Relative inductive voltage drop2.1%

Identification

4EP3603-6DS00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EP3603-6DS00 — Electrical
ParameterValue
Rated operating voltage500V
Rated current (AC)12A
Number of phases3
Current (AC), max.12A
Rated current (DC)14.7A
Voltage typeAC
Rated operating frequency50Hz

Losses & Thermal

4EP3603-6DS00 — Losses & Thermal
ParameterValue
Power loss, coil (W)20W
Power loss, iron core (W)12W
Rated ambient temperature50°C

Approvals

4EP3603-6DS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP3603-6DS00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals / tab terminals
IP protection ratingIP00
Height0.125m
Width0.125m
Depth0.09m

Product details

What it is and what it does

The Siemens 4EP3603-6DS00 is a three-phase commutating choke (line reactor) designed for converter output circuits. It limits the rate of rise of current (di/dt) and smooths commutation notches, protecting the converter's power semiconductors and reducing harmonic distortion on the motor cables. Rated for 12 A AC continuous current at 50 Hz and 500 V, with a DC current rating of 14.7 A. The 0.0016 H inductance gives a relative inductive voltage drop of 2.1% at rated conditions. Thermal class B insulation, with 20 W copper loss and 12 W iron loss at rated load, and a 50 °C ambient rating.

Mounting and integration

IP00 open-frame construction — no enclosure, no finger-safe protection. The 0.125 m × 0.125 m × 0.09 m footprint (W×H×D) fits a standard sub-panel layout. Terminals are screw-type and tab connections for the main current circuit. Cable gauge matches 12 A continuous duty.

Frequently asked questions

Will 4EP3603-6DS00 drop into a panel specified around 5SJ3140-7 without rewiring?

No. The 5SJ3140-7 is a 1-pole miniature circuit breaker (MCB) with a completely different form factor, mounting method (DIN rail), and terminal arrangement. The 4EP3603-6DS00 is a 3-phase choke with screw/tab terminals for panel-mount; there is no mechanical or electrical interchangeability.

MPN
4EP3603-6DS00