Skip to main content
Siemens 4EP3605-0AS00 — Line/Load Reactors

Siemens 4EP3605-0AS00 Commutating Choke, 3-Phase 230V AC, 56

MPN4EP3605-0AS00

Siemens SENTRON series, commutating choke for converter, 3-phase, 230V AC, 56A maximum / 50A rated, 0.15 mH, IP00, screw-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EP3605-0AS00 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitscrew-type terminals
Operating voltage rated value230V
Relative inductive drop in voltage on the measurement level current, voltage and frequency2%
Operating frequency rated value50Hz
Phase number3
Ambient temperature rated value40°C
Thermal class acc. to IEC 60085B
Rated value50A
At DC rated value68.6A
Protection class IPIP00
Inductivity rated value0.00015H

Product details

The Siemens 4EP3605-0AS00 is a three-phase commutating choke (line reactor) designed for converter front-ends. It limits current rise during commutation, reducing harmonic distortion and protecting the DC link from switching transients. Rated for 50 A continuous with a 56 A maximum thermal current (Ithmax) at 50 Hz, 230 V AC three-phase. The 0.15 mH inductance (0.147 mH per the spec line) gives a 2 % relative inductive voltage drop — meaning it's sized for moderate impedance, not heavy filtering.

The 56 A maximum (Ithmax) is the thermal limit under worst-case conditions — the choke can handle short-term overloads up to that level without exceeding Class B insulation temperature rise (ambient 40 °C). The 50 A rated current (I LN) is the continuous design point for normal operation. At DC, the rated value is 68.6 A — relevant if the choke is used on the DC side of a converter, though the primary application is AC line-side commutation. Screw-type terminals accept standard lug or ring-terminal connections.

Mounts in the AC line between the supply and the converter input, typically in a control cabinet. The open-frame design (IP00) requires clean, dry, non-conductive surroundings — not for washdown or outdoor use without an enclosure. Rated ambient temperature is 40 °C with Class B insulation, so derating is needed if cabinet internal temperature exceeds that. The 50 Hz operating frequency is standard for mains applications.

Frequently asked questions

What is the maximum current rating of 4EP3605-0AS00?

The maximum thermal current (Ithmax) is 56 A at 50 Hz. The continuous rated current (I LN) is 50 A.

Will 4EP3605-0AS00 drop into a panel specified around 5SL3232-6MB?

No — the 5SL3232-6MB is a miniature circuit breaker (MCB), a completely different component class. The 4EP3605-0AS00 is a three-phase choke for converter input; it serves a different function and has a different footprint.

MPN
4EP3605-0AS00