Skip to main content
Siemens 4EP3700-1DS00 — Line/Load Reactors

Siemens 4EP3700-1DS00 Commutating Choke, 22.5 A, 0.0015 H

MPN4EP3700-1DS00

Siemens SENTRON 4EP3700-1DS00, 3-phase commutating choke for converters, 22.5 A rated, 0.0015 H, 500 V AC, IP00, screw-type terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP3700-1DS00 — Inductance & Impedance
ParameterValue
Rated inductance0.0015H
Relative inductive voltage drop4%

Identification

4EP3700-1DS00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EP3700-1DS00 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Rated current (DC)30.6A
Voltage typeAC
Rated operating frequency50Hz

Losses & Thermal

4EP3700-1DS00 — Losses & Thermal
ParameterValue
Power loss, coil (W)55W
Power loss, iron core (W)13.4W
Rated ambient temperature40°C

Approvals

4EP3700-1DS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP3700-1DS00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.153m
Width0.178m
Depth0.105m

Product details

What it is and what it does

The Siemens 4EP3700-1DS00 is a 3-phase commutating choke (line reactor) for converter applications, rated 22.5 A continuous with a maximum of 25 A. Its 0.0015 H inductance limits current rise and harmonics on the AC side of a variable-frequency drive or DC drive converter, protecting both the rectifier and the upstream supply. The 4% relative inductive voltage drop at rated conditions is a standard sizing target for drive input chokes — high enough to smooth line notching, low enough to avoid excessive voltage sag under load. The part carries a DC-rated current of 30.6 A, which may be relevant if the choke is used in a DC-link application, though the primary duty is AC line input. Screw-type terminals simplify field wiring for panel builders, and the IP00 enclosure means it must be mounted inside a cabinet or enclosure that provides the required touch protection.

Where it fits in the panel

The 4EP3700-1DS00 measures 0.178 m wide, 0.105 m deep, and 0.153 m tall. It bolts directly to a mounting plate. Screw terminals accept main circuit conductors. Thermal class B insulation allows full load at 40 °C ambient.

Power loss and thermal management

Power loss at rated load is 55 W in the coil and 13.4 W in the iron core. That heat must be dissipated inside the enclosure.

Frequently asked questions

Will 4EP3700-1DS00 drop into a panel specified around 5SL6606-7YA?

No — 5SL6606-7YA is a 4-pole miniature circuit breaker with a completely different form factor and function. The 4EP3700-1DS00 is a bolted-mount choke, not a DIN-rail breaker; rewiring and a different mounting footprint would be required.

MPN
4EP3700-1DS00