Siemens 4EP3701-5DS00 — Line/Load Reactors

Siemens 4EP3701-5DS00 Commutating Choke, 25A AC, 400V, 0.89m

MPN4EP3701-5DS00
Active

Siemens 4EP3701-5DS00, commutating choke for converter, 3-phase, 400V AC, 25A AC max, 0.89mH, IP00, screw terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP3701-5DS00 — Inductance & Impedance
ParameterValue
Rated inductance0.00089H
Relative inductive voltage drop4%

Identification

4EP3701-5DS00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EP3701-5DS00 — Electrical
ParameterValue
Rated operating voltage400V
Rated current (AC)22.5A
Number of phases3
Current (AC), max.25A
Rated current (DC)30.6A
Voltage typeAC
Rated operating frequency50Hz
Peak current31A

Losses & Thermal

4EP3701-5DS00 — Losses & Thermal
ParameterValue
Power loss, coil (W)53W
Power loss, iron core (W)9W
Rated ambient temperature40°C

Approvals

4EP3701-5DS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP3701-5DS00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.153m
Width0.178m
Depth0.105m

Product details

The Siemens 4EP3701-5DS00 is a 3-phase commutating choke (line reactor) designed for converter front-ends. It's rated for 400V AC at 50 Hz, with a maximum AC current of 25A and a rated inductance of 0.89 mH. The relative inductive voltage drop at rated current, voltage, and frequency is 4% — a standard figure for this class of choke, meaning it provides enough impedance to limit di/dt and smooth commutation notches without excessive voltage drop under load.

Sizing and thermal class

The choke carries a rated operational AC current of 22.5 A and a DC rated current of 30.6 A, so it's sized for a converter DC bus pulling up to that DC level. The thermal class is B per IEC 60085, with a 40°C ambient rating. Copper losses (coil) are 53 W, iron losses 9 W — total 62 W dissipated in free air. The IP00 enclosure means it's an open-frame component for cabinet mounting; no washdown or dust protection, so panel ventilation must handle the heat.

Mounting and connections

Dimensions are 0.178 m wide, 0.153 m high, 0.105 m deep — a compact footprint for a 25 A three-phase choke. Main circuit connections are screw-type terminals, which simplifies panel wiring with ring or fork lugs. No DIN-rail clip; it's a foot-mount chassis unit that bolts to the panel backplate.

Frequently asked questions

What are the key electrical ratings for 4EP3701-5DS00?

Three-phase commutating choke rated 400V AC, 50 Hz. Maximum AC current 25A, rated operational AC current 22.5A, DC rated current 30.6A. Inductance 0.89 mH, relative inductive voltage drop 4%.

Where can I buy 4EP3701-5DS00?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What is the thermal class and ambient rating?

Thermal class B per IEC 60085, rated for 40°C ambient. Copper losses 53W, iron losses 9W.

MPN
4EP3701-5DS00