Skip to main content
Siemens 4EP3800-1AK00 — Line/Load Reactors

Siemens SIDAC 4EP3800-1AK00 Output Reactor, 17 A, 8 kHz

MPN4EP3800-1AK00

Siemens SIDAC output reactor, 3-phase AC, 17 A max, 8 kHz rated frequency, 0.25 mH, IP00, screw terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EP3800-1AK00 — Inductance & Impedance
ParameterValue
Rated inductance0.00025H
4EP3800-1AK00 — Identification
ParameterValue
Product designationoutput reactor
4EP3800-1AK00 — Electrical
ParameterValue
Number of phases3
Voltage typeAC
4EP3800-1AK00 — Losses & Thermal
ParameterValue
Power loss, coil (W)33W
Power loss, iron core (W)20W
Rated ambient temperature40°C
4EP3800-1AK00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EP3800-1AK00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.15m
Width0.17m
Depth0.12m

Product details

What this output reactor does

The Siemens SIDAC 4EP3800-1AK00 is a 3-phase AC output reactor rated for a maximum continuous current of 17 A and a rated switching frequency of 8 000 Hz. Its 0.25 mH inductance limits the rate of current rise (di/dt) from the drive output, protecting the motor windings and cable insulation from voltage spikes caused by long cable runs or fast-switching IGBTs. The IP00 open-chassis design means it mounts inside a panel or enclosure that provides the physical and environmental protection — it is not a standalone outdoor device.

The 17 A maximum is the thermal current rating at 40 °C ambient (per the datasheet conditions). If your drive output is rated for 16 A continuous, this reactor is correctly sized; if the drive is rated for 20 A, you need a larger reactor. The 8 000 Hz rated frequency matches the typical switching frequency of many modern PWM drives — confirm your drive's carrier frequency does not exceed this value, or the core may saturate and overheat. Total power loss sums to 53 W (33 W coil + 20 W iron core), which must be dissipated inside the enclosure; factor that into your panel thermal budget.

Integration notes

Dimensions are 0.17 m wide × 0.15 m high × 0.12 m deep. Thermal class B per IEC 60085 means the insulation system is rated for a maximum hot-spot temperature of 130 °C, which is typical for general-purpose reactors in industrial drives. Mounting is inside a panel; the IP00 protection class means no ingress protection on its own, so the enclosure must provide the required IP rating for the environment.

Frequently asked questions

What are the key electrical ratings of the 4EP3800-1AK00?

The 4EP3800-1AK00 is a 3-phase AC output reactor rated for a maximum current of 17 A, a rated switching frequency of 8 000 Hz, and an inductance of 0.25 mH. The coil power loss is 33 W and the iron core loss is 20 W at 40 °C ambient.

Where can I buy the 4EP3800-1AK00?

The 4EP3800-1AK00 is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the physical dimensions of the 4EP3800-1AK00?

The dimensions are 0.17 m width, 0.15 m height, and 0.12 m depth. The terminals are screw-type for the main current circuit.

MPN
4EP3800-1AK00