Skip to main content
Siemens 4EP3800-2DS00 — Line/Load Reactors

Siemens 4EP3800-2DS00 Commutating Choke, 3-Phase 400V 36A

MPN4EP3800-2DS00
Active

Siemens 4EP3800-2DS00, commutating choke for converter, 3-phase, 400V AC, 36A rated, 0.56mH, IP00, screw terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EP3800-2DS00 — Inductance & Impedance
ParameterValue
Rated inductance0.00056H
Relative inductive voltage drop4%
4EP3800-2DS00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EP3800-2DS00 — Electrical
ParameterValue
Rated operating voltage400V
Rated current (AC)36A
Number of phases3
Current (AC), max.40A
Rated current (DC)49A
Voltage typeAC
Rated operating frequency50Hz
Peak current50A
4EP3800-2DS00 — Losses & Thermal
ParameterValue
Power loss, coil (W)60W
Power loss, iron core (W)14.5W
Rated ambient temperature40°C
4EP3800-2DS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EP3800-2DS00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.153m
Width0.178m
Depth0.12m

Product details

The Siemens 4EP3800-2DS00 is a 3-phase commutating choke designed for converter applications. This choke limits the rate of current rise and smooths commutation notches on the line side of a converter — essential for reducing harmonic distortion and protecting upstream components.

The 36A AC rated current and 40A maximum AC current define the continuous and peak load capability. The DC rated current of 49A and peak current of 50A cover the DC-link side — useful when sizing for a drive with a higher DC bus ripple. The 4% voltage drop is the impedance at rated conditions; a higher drop means more smoothing but also more voltage loss, so match it to the drive's tolerance. Thermal class B means the winding insulation withstands 130°C hot-spot temperature, adequate for most industrial converter cabinets at 40°C ambient.

The choke measures 0.178 m wide, 0.153 m high, and 0.12 m deep. Connections are via screw-type terminals, so no special crimp tooling is needed. The total power loss is 60 W in the coil plus 14.5 W in the iron core — account for that heat in the enclosure's thermal budget.

It is a mature, standard catalog item — not a special or a phase-out line.

Frequently asked questions

What is the 4EP3800-2DS00 used for?

It is a 3-phase commutating choke for converter applications, rated 400V AC, 36A, 0.56 mH. It limits current rise and smooths commutation notches on the line side of a converter or drive.

What are the key specifications of 4EP3800-2DS00?

3-phase, 400V AC, 50 Hz, 36A rated AC current, 40A max AC, 49A DC rated, 50A peak, 0.56 mH, 4% voltage drop, thermal class B, IP00, screw terminals, dimensions 0.178 x 0.153 x 0.12 m.

Where can I buy 4EP3800-2DS00 and how is it quoted?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

MPN
4EP3800-2DS00