Skip to main content
Siemens 4EP3801-0MS00 — Line/Load Reactors

Siemens SIDAC 4EP3801-0MS00 Filter Reactor, 400V 11.8A 5.67%

MPN4EP3801-0MS00

Siemens SIDAC series, 4EP3801-0MS00 filter reactor, 3-phase, 400V AC, 11.8A rated current, 5.67% relative throttling factor, 210Hz resonant frequency, IP00, screw terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP3801-0MS00 — Inductance & Impedance
ParameterValue
Rated inductance0.0041H
Relative throttling factor5.67%
Filter resonant frequency210Hz
Rated reactive power (filter bank)7 500var

Identification

4EP3801-0MS00 — Identification
ParameterValue
Product designationfilter reactor

Electrical

4EP3801-0MS00 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz

Losses & Thermal

4EP3801-0MS00 — Losses & Thermal
ParameterValue
Total power loss (W)62W
Rated ambient temperature40°C

Approvals

4EP3801-0MS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP3801-0MS00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.153m
Width0.178m
Depth0.12m

Product details

What this reactor does in the drive line

The Siemens SIDAC 4EP3801-0MS00 is a 3-phase filter reactor rated for 400 V AC at 50 Hz, carrying 11.8 A continuous with a 13.2 A maximum. Its 0.0041 H inductance and 5.67% relative throttling factor are sized to limit harmonic distortion and reduce voltage notching on the drive input.

Mounting and integration constraints

At 0.178 m wide, 0.153 m tall, and 0.12 m deep, this reactor occupies a footprint roughly the size of a standard contactor but with more depth allowance for the core and winding overhang.

Reactive power and filter bank application

The filter bank's rated reactive power is 7 500 var (7.5 kvar), which places this reactor in the range used for small to medium drives — typically 5.5 to 11 kW motors depending on the drive's DC-link configuration and the desired harmonic mitigation level. The 5.67% impedance is a common value for line reactors in IEC markets; it provides enough inductance to limit inrush current and reduce harmonic current draw without causing excessive voltage drop under full load. For applications requiring tighter harmonic control (IEEE 519 compliance), a higher-impedance reactor or a passive filter stage would be needed downstream.

MPN
4EP3801-0MS00