Skip to main content
Siemens 4EP3804-2BK00 — Line/Load Reactors

Siemens SIDAC 4EP3804-2BK00 Output Reactor, 17A 6.4 kHz

MPN4EP3804-2BK00

Siemens SIDAC output reactor, 3-phase, 600V, 17A max, 6.4 kHz rated frequency, 0.3 mH, IP00, Class B insulation, screw/tab terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP3804-2BK00 — Inductance & Impedance
ParameterValue
Rated inductance0.0003H

Identification

4EP3804-2BK00 — Identification
ParameterValue
Product designationoutput reactor

Electrical

4EP3804-2BK00 — Electrical
ParameterValue
Number of phases3
Voltage typeAC

Losses & Thermal

4EP3804-2BK00 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C

Approvals

4EP3804-2BK00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP3804-2BK00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals / tab terminals
IP protection ratingIP00
Height0.15m
Width0.17m
Depth0.12m

Other specifications

4EP3804-2BK00 — Other specifications
ParameterValue
Rated value6 400Hz

Product details

The Siemens SIDAC 4EP3804-2BK00 is a 3-phase output reactor rated for 600 V AC, with a maximum continuous current of 17 A and a rated frequency of 6.4 kHz. Its 0.3 mH inductance (LN) and 9.2% impedance (UK) are sized to limit the rate of voltage rise (dV/dt) and peak currents from a VFD's PWM output, protecting the motor windings and extending cable runs. The IP00 enclosure means it's an open-frame component intended for installation inside a panel or cabinet — no washdown or outdoor exposure.

Sizing and fit

The 4EP3804-2BK00 is designed for a 3-phase AC output from a variable-frequency drive, not a line reactor. The 6.4 kHz rated frequency matches the typical switching frequency of many modern IGBT-based drives — if your drive's carrier frequency is set to 4 kHz or 8 kHz, this reactor still works, but the core losses and temperature rise will differ. The 0.3 mH inductance and 17 A rating pair with a motor load of roughly 15.3 A (I LN), which is the nominal current the reactor is optimized for at 40°C ambient.

Integration notes

Dimensions are 0.17 m wide, 0.15 m tall, and 0.12 m deep — a compact block that fits on a standard backplate or DIN-rail adapter plate. Connection is via screw-type or tab terminals for the main circuit, so no special crimp tooling is required. The Class B insulation system (130°C) and 40°C ambient rating are standard for general-purpose industrial environments.

Frequently asked questions

Where can I buy 4EP3804-2BK00 and how do I get a price?

This part is sourced through independent distribution and is quoted to order against an RFQ. Submit an RFQ and availability and current pricing will be confirmed at quote time.

What are the key specifications of 4EP3804-2BK00?

It is a 3-phase output reactor rated 600 V AC, 17 A max, 6.4 kHz rated frequency, 0.3 mH inductance, IP00, Class B insulation, with screw-type or tab terminals.

MPN
4EP3804-2BK00