Skip to main content
Siemens 4EP3804-2BK00 — Line/Load Reactors

Siemens SIDAC 4EP3804-2BK00 Output Reactor, 17A 6.4 kHz

MPN4EP3804-2BK00

Siemens SIDAC output reactor, 3-phase, 600V, 17A max, 6.4 kHz rated frequency, 0.3 mH, IP00, Class B insulation, screw/tab terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EP3804-2BK00 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitscrew-type terminals / tab terminals
Phase number3
Ambient temperature rated value40°C
Depth0.12m
Width0.17m
Height0.15m
Thermal class acc. to IEC 60085B
Rated value6 400Hz
Protection class IPIP00
Inductivity rated value0.0003H

Product details

The Siemens SIDAC 4EP3804-2BK00 is a 3-phase output reactor rated for 600 V AC, with a maximum continuous current of 17 A and a rated frequency of 6.4 kHz. Its 0.3 mH inductance (LN) and 9.2% impedance (UK) are sized to limit the rate of voltage rise (dV/dt) and peak currents from a VFD's PWM output, protecting the motor windings and extending cable runs.

The 4EP3804-2BK00 is designed for a 3-phase AC output from a variable-frequency drive, not a line reactor. The 6.4 kHz rated frequency matches the typical switching frequency of many modern IGBT-based drives — if your drive's carrier frequency is set to 4 kHz or 8 kHz, this reactor still works, but the core losses and temperature rise will differ. The 0.3 mH inductance and 17 A rating pair with a motor load of roughly 15.3 A (I LN), which is the nominal current the reactor is optimized for at 40°C ambient.

Integration notes

Dimensions are 0.17 m wide, 0.15 m tall, and 0.12 m deep — a compact block that fits on a standard backplate or DIN-rail adapter plate. Connection is via screw-type or tab terminals for the main circuit, so no special crimp tooling is required. The Class B insulation system (130°C) and 40°C ambient rating are standard for general-purpose industrial environments.

Frequently asked questions

Where can I buy 4EP3804-2BK00 and how do I get a price?

This part is sourced through independent distribution and is quoted to order against an RFQ. Submit an RFQ and availability and current pricing will be confirmed at quote time.

What are the key specifications of 4EP3804-2BK00?

It is a 3-phase output reactor rated 600 V AC, 17 A max, 6.4 kHz rated frequency, 0.3 mH inductance, IP00, Class B insulation, with screw-type or tab terminals.

MPN
4EP3804-2BK00