Skip to main content
Siemens 4EP3901-3MS00 — Line/Load Reactors

SIDAC 4EP3901-3MS00 Filter Reactor, 480 V 60 Hz 15.6 A

MPN4EP3901-3MS00

SIDAC 4EP3901-3MS00, 3-phase filter reactor, 480 V AC, 60 Hz, rated 15.6 A (max 17.3 A), 7 % relative throttling, 12.5 kvar, IP00, screw/tab terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EP3901-3MS00 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitscrew-type terminals / tab terminals
Operating voltage rated value480V
Power loss [W]73.6W
Reactive power of the filter bank rated value12 500var
Operating frequency rated value60Hz
Resonant frequency of the filter227Hz
Phase number3
Ambient temperature rated value40°C
Depth0.123m
Width0.219m
Height0.179m
Thermal class acc. to IEC 60085B
Rated value15.6A
Protection class IPIP00
Inductivity rated value0.0037H
Relative throttling factor7%

Product details

What this reactor does in a panel

The SIDAC 4EP3901-3MS00 is a 3-phase filter reactor rated for 480 V AC at 60 Hz, carrying a continuous rated current of 15.6 A with a maximum of 17.3 A. The 7 % relative throttling factor and 0.0037 H inductance shape the harmonic profile at the line input; the 227 Hz resonant frequency means it traps the 5th harmonic (300 Hz on a 60 Hz fundamental) and attenuates higher-order ripple. Reactive power of the filter bank is 12.5 kvar. Thermal class B (130 °C rise) per IEC 60085 keeps the winding temperature within limits at the rated 40 °C ambient. Power loss runs 73.6 W at full load — plan for that heat inside the enclosure.

Dimensions are 0.219 m wide × 0.179 m high × 0.123 m deep; the footprint fits a standard backplate, but the 0.123 m depth eats into the gland-plate clearance. Terminals are screw-type and tab connections on the main circuit — torque to the manufacturer's spec for the lug size you choose. No DIN-rail clip; it bolts directly to the mounting surface.

Frequently asked questions

Will 4EP3901-3MS00 drop into a panel that was specified around 5SJ3140-7 without rewiring?

No — 5SJ3140-7 is a single-pole 240 V miniature circuit breaker (MCB), not a filter reactor. They serve completely different functions: the MCB protects branch circuits; this reactor filters harmonics. No direct drop-in replacement.

What compliance documentation does 4EP3901-3MS00 carry?

The description notes UL/CSA recognition per EN 61558-2-20. No RoHS or REACH declaration is on the record here — confirm with the manufacturer or distributor at order time.

MPN
4EP3901-3MS00