Skip to main content
Siemens 4EP4000-0DS00 — Line/Load Reactors

Siemens 4EP4000-0DS00 Commutating Choke, 63 A, 400 V AC

MPN4EP4000-0DS00

Siemens 4EP4000-0DS00 commutating choke for converters, 3-phase, 400 V AC, 63 A max / 56.7 A rated, 0.45 mH, IP00, flat-type terminals, UL/CSA recognized.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EP4000-0DS00 — Inductance & Impedance
ParameterValue
Rated inductance0.00045H
Relative inductive voltage drop4%
4EP4000-0DS00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EP4000-0DS00 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Rated current (DC)77.2A
Voltage typeAC
Rated operating frequency50Hz
4EP4000-0DS00 — Losses & Thermal
ParameterValue
Power loss, coil (W)71W
Power loss, iron core (W)33W
Rated ambient temperature40°C
4EP4000-0DS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EP4000-0DS00 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.179m
Width0.219m
Depth0.143m

Product details

What this choke does in your drive circuit

It limits current rise and harmonics on the input side of a variable-frequency drive or DC drive, protecting the rectifier diodes and reducing line notching. Rated at 56.7 A continuous with a 63 A maximum, with an inductance of 0.00045 H and a 4% relative inductive voltage drop at rated conditions. Thermal class B insulation per IEC 60085, rated for a 40 °C ambient. Total power loss at rated load is 104 W (71 W coil + 33 W iron core) — that heat has to be dissipated into the enclosure air; plan for ventilation or derating if the panel runs hot.

Mounting and connection reality

IP00 — no enclosure, no touch protection. Dimensions are 0.219 m wide × 0.179 m tall × 0.143 m deep, so it takes up about the footprint of a small contactor but with more depth. Main circuit connects via flat-type terminals — expect bus-bar or ring-tongue lugs, not spring-cage or screw-clamp.

Lifecycle status is listed as mature — meaning it is a stable, long-running design, not recently introduced and not flagged for discontinuation.

Frequently asked questions

Will 4EP4000-0DS00 drop into a panel specified around 5SJ3140-7?

No — those are completely different device classes. The 5SJ3140-7 is a single-pole miniature circuit breaker (MCB) rated 40 A at 240 V AC. The 4EP4000-0DS00 is a 3-phase commutating choke for converter input circuits. They are not form-fit-function interchangeable and serve different roles in the panel.

MPN