Skip to main content
Siemens 4EP4000-2US00 — Line/Load Reactors

Siemens 4EP4000-2US00 Mains Choke, 3-Phase 100A AC, IP00

MPN4EP4000-2US00
Active

Siemens 4EP4000-2US00, mains choke (Netzdrossel f. FU), 3-phase AC, 400/480V, 100A max, 0.14mH, IP00, flat-type terminals.

$454.66Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EP4000-2US00 — Inductance & Impedance
ParameterValue
Rated inductance0.00014H
Relative inductive voltage drop2%
4EP4000-2US00 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EP4000-2US00 — Electrical
ParameterValue
Rated operating voltage400, 480V
Rated current (AC)90A
Number of phases3
Current (AC), max.100A
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EP4000-2US00 — Losses & Thermal
ParameterValue
Power loss, coil (W)73W
Power loss, iron core (W)30W
Rated ambient temperature40°C
4EP4000-2US00 — Approvals
ParameterValue
Thermal class (IEC 60085)B
4EP4000-2US00 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.179m
Width0.219m
Depth0.143m

Product details

The Siemens 4EP4000-2US00 is a three-phase mains choke — Netzdrossel für Frequenzumrichter — sized for the input side of a variable-frequency drive. It sits between the supply and the drive's rectifier, smoothing line harmonics and limiting inrush current. Rated for 400/480 V AC at 50/60 Hz, it carries a maximum AC current of 100 A and a rated operational current of 90 A. Inductance is 0.00014 H (0.14 mH) with a 2% relative inductive voltage drop at rated conditions. The 73 W coil loss plus 30 W iron core loss (103 W total at rated conditions) needs to be cleared from the enclosure; IP00 means it is an open-frame component, so the panel's own airflow must handle the heat.

The main circuit connects via flat-type terminals — expect busbar or crimp-lug terminations, not screw-clamp wire ports. Dimensions are 0.219 m wide by 0.179 m tall by 0.143 m deep. It is an open-chassis unit (IP00), so it mounts inside a cabinet, not on a panel surface. Thermal class B per IEC 60085 means the insulation system is rated for a 130 °C maximum hot-spot temperature, which aligns with the 40 °C ambient rating.

Production status and sourcing

That means it is still a standard catalog line item from Siemens — no last-time-buy window, no forced migration to a successor.

Frequently asked questions

Where can I buy 4EP4000-2US00 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance documentation does Siemens provide for 4EP4000-2US00?

The part carries UL/CSA recognition per EN 61558-2-20. Standard Siemens documentation includes the declaration of conformity for the applicable EU directives; RoHS and REACH compliance data is available through the manufacturer's product support portal.

What are the key electrical ratings for 4EP4000-2US00?

Three-phase AC, 400/480 V rated voltage, 50/60 Hz, 100 A maximum AC current, 90 A rated operational current, 0.14 mH inductance, 2% inductive voltage drop at rated conditions.

MPN
4EP4000-2US00