Line Reactor for VFD Input
Rated at 500 V AC, 50 Hz, it handles a maximum continuous current of 71 A and a rated operational current of 63.9 A. Thermal class B (130 °C rise) and a 78 W coil loss plus 21.5 W iron loss at full load give you the thermal budget to size panel ventilation.
Mounting and Connection
IP00 — no enclosure, so it mounts inside a panel or cabinet where the environment is clean and dry. The flat-type terminals (flat connector) accept standard busbar or cable lugs; no DIN-rail clip, so plan for bolt-down or bracket mounting. Dimensions: 0.219 m wide, 0.179 m tall, 0.143 m deep — leave clearance for airflow and terminal access.