Skip to main content
Siemens 4EP4002-2DS00 — Line/Load Reactors

Siemens 4EP4002-2DS00 Commutating Choke, 71A / 63.9A, 0.52 m

MPN4EP4002-2DS00

Siemens 4EP4002-2DS00 commutating choke for converter, 3-phase, 500V AC, 71A max / 63.9A rated, 0.52 mH, IP00, flat-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EP4002-2DS00 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value500V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Power loss [W] of the coil80W
Power loss [W] of the iron core34W
Operating frequency rated value50Hz
Phase number3
Ambient temperature rated value40°C
Depth0.143m
Width0.219m
Height0.179m
Thermal class acc. to IEC 60085B
Rated value63.9A
At DC rated value87A
Protection class IPIP00
Inductivity rated value0.00052H

Product details

It limits current rise and harmonics on the line side of a variable-frequency drive or DC drive, protecting the converter's input rectifier and smoothing the DC bus. The 0.52 mH inductance at 71 A maximum (63.9 A rated continuous) and 500 V AC operating voltage is sized for medium-power drives in the 30–50 kW range, depending on the drive's DC-link configuration.

The 71 A maximum current (Ithmax) at 50 Hz is the thermal limit under worst-case conditions — the choke can handle this continuously without exceeding the Class B (130 °C) insulation system. The 63.9 A rated current (ILN) is the nominal design point for voltage drop calculations. The 4 % relative inductive voltage drop (Uk) at rated current and frequency means the choke will drop about 20 V at 500 V / 63.9 A — a standard value for most drive line reactors. The 87 A DC rating confirms it can also serve in DC-link applications, though the primary role is AC line-side commutation.

The flat-type terminals (flat connector) accept busbar or cable lugs; plan for M8 or M10 ring terminals depending on your lug size. Dimensions are 0.219 m wide × 0.179 m high × 0.143 m deep — about the footprint of a small shoe box. Mounting is via the baseplate; no DIN-rail clip is provided. The 80 W coil loss plus 34 W iron core loss (114 W total) must be considered in your panel thermal budget — allow ventilation around the choke or derate ambient if the cabinet is sealed.

Frequently asked questions

What is the 4EP4002-2DS00 used for?

It is a 3-phase commutating choke (line reactor) for converter/drive applications. It limits current rise, reduces harmonics, and protects the input rectifier of a variable-frequency drive or DC drive.

What are the key specifications of the 4EP4002-2DS00?

3-phase, 500 V AC, 71 A maximum / 63.9 A rated current, 0.52 mH inductance, 4 % voltage drop, IP00, Class B insulation (130 °C), flat-type terminals. Dimensions: 0.219 m × 0.179 m × 0.143 m.

Where can I buy the 4EP4002-2DS00?

This part is sourced to order through our independent distribution channel. Submit an RFQ for current availability and pricing — we confirm both at quote time.

Will the 4EP4002-2DS00 drop into a panel designed for a 5SJ3140-7 circuit breaker?

No. The 4EP4002-2DS00 is a 3-phase line reactor (choke), while the 5SJ3140-7 is a 1-pole miniature circuit breaker. They serve completely different functions and have different footprints, terminals, and mounting methods. No direct interchange exists.

MPN