Siemens 4EP4002-2DS00 — Line/Load Reactors

Siemens 4EP4002-2DS00 Commutating Choke, 71A / 63.9A, 0.52 m

MPN4EP4002-2DS00

Siemens 4EP4002-2DS00 commutating choke for converter, 3-phase, 500V AC, 71A max / 63.9A rated, 0.52 mH, IP00, flat-type terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP4002-2DS00 — Inductance & Impedance
ParameterValue
Rated inductance0.00052H
Relative inductive voltage drop4%

Identification

4EP4002-2DS00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EP4002-2DS00 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Rated current (DC)87A
Voltage typeAC
Rated operating frequency50Hz

Losses & Thermal

4EP4002-2DS00 — Losses & Thermal
ParameterValue
Power loss, coil (W)80W
Power loss, iron core (W)34W
Rated ambient temperature40°C

Approvals

4EP4002-2DS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP4002-2DS00 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.179m
Width0.219m
Depth0.143m

Product details

What It Is and What It Does

The Siemens 4EP4002-2DS00 is a 3-phase commutating choke (line reactor) designed for converter (drive) applications. It limits current rise and harmonics on the line side of a variable-frequency drive or DC drive, protecting the converter's input rectifier and smoothing the DC bus. The 0.52 mH inductance at 71 A maximum (63.9 A rated continuous) and 500 V AC operating voltage is sized for medium-power drives in the 30–50 kW range, depending on the drive's DC-link configuration.

Key Ratings and What They Mean for Fit

The 71 A maximum current (Ithmax) at 50 Hz is the thermal limit under worst-case conditions — the choke can handle this continuously without exceeding the Class B (130 °C) insulation system. The 63.9 A rated current (ILN) is the nominal design point for voltage drop calculations. The 4 % relative inductive voltage drop (Uk) at rated current and frequency means the choke will drop about 20 V at 500 V / 63.9 A — a standard value for most drive line reactors. The 87 A DC rating confirms it can also serve in DC-link applications, though the primary role is AC line-side commutation.

Integration and Mounting

IP00 means no enclosure — this choke is intended for installation inside a panel or cabinet where it is protected from dust and moisture. The flat-type terminals (flat connector) accept busbar or cable lugs; plan for M8 or M10 ring terminals depending on your lug size. Dimensions are 0.219 m wide × 0.179 m high × 0.143 m deep — about the footprint of a small shoe box. Mounting is via the baseplate; no DIN-rail clip is provided. The 80 W coil loss plus 34 W iron core loss (114 W total) must be considered in your panel thermal budget — allow ventilation around the choke or derate ambient if the cabinet is sealed.

Frequently asked questions

What is the 4EP4002-2DS00 used for?

It is a 3-phase commutating choke (line reactor) for converter/drive applications. It limits current rise, reduces harmonics, and protects the input rectifier of a variable-frequency drive or DC drive.

What are the key specifications of the 4EP4002-2DS00?

3-phase, 500 V AC, 71 A maximum / 63.9 A rated current, 0.52 mH inductance, 4 % voltage drop, IP00, Class B insulation (130 °C), flat-type terminals. Dimensions: 0.219 m × 0.179 m × 0.143 m.

Where can I buy the 4EP4002-2DS00?

This part is sourced to order through our independent distribution channel. Submit an RFQ for current availability and pricing — we confirm both at quote time.

Will the 4EP4002-2DS00 drop into a panel designed for a 5SJ3140-7 circuit breaker?

No. The 4EP4002-2DS00 is a 3-phase line reactor (choke), while the 5SJ3140-7 is a 1-pole miniature circuit breaker. They serve completely different functions and have different footprints, terminals, and mounting methods. No direct interchange exists.

MPN
4EP4002-2DS00