Skip to main content
Siemens 4EP4002-3DS00 — Line/Load Reactors

Siemens 4EP4002-3DS00 Commutating Choke, 91A, 400V, 3-Phase

MPN4EP4002-3DS00

Siemens 4EP4 series commutating choke for converters, 4EP4002-3DS00, 3-phase, 400V AC, 50Hz, 91A max / 81.9A rated, 0.31mH, IP00, flat-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EP4002-3DS00 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value400V
Relative inductive drop in voltage on the measurement level current, voltage and frequency4%
Power loss [W] of the coil72.6W
Power loss [W] of the iron core35.8W
Operating frequency rated value50Hz
Phase number3
Ambient temperature rated value40°C
Depth0.143m
Width0.219m
Height0.179m
Thermal class acc. to IEC 60085B
Rated value81.9A
At DC rated value111.5A
Protection class IPIP00
Inductivity rated value0.00031H

Product details

The Siemens 4EP4002-3DS00 is a 3-phase commutating choke (line reactor) for converter applications, rated 400V AC at 50Hz. It handles a maximum continuous current of 91A and a rated current of 81.9A, with a DC-rated value of 111.5A. The inductance is 0.31mH, and the relative inductive voltage drop is 4% at rated current, frequency, and voltage — a standard value for limiting current rise and harmonics on the line side of a drive.

The 91A maximum current (81.9A rated) and 111.5A DC rating tell you this choke is sized for a drive drawing around 75–90A continuous on the line side. The 4% inductive voltage drop is typical for a commutating choke — it provides enough impedance to smooth commutation notches and limit di/dt without dropping excessive voltage under load. The 72.6W coil loss plus 35.8W iron-core loss (108.4W total at rated conditions) is heat that must be dissipated; with IP00, the choke is open-frame and relies on cabinet airflow — no enclosure to trap heat, but also no protection from dust or accidental contact.

Dimensions: 0.219m wide, 0.179m high, 0.143m deep. This is a panel-mount component, not a DIN-rail snap-on — it bolts into the cabinet. The 0.143m (143mm) depth is the front-to-back dimension; allow clearance for the flat-type terminal connections and bending radius of the incoming cables. IP00 means no finger-safe enclosure, so it belongs behind a locked panel door or inside a dedicated drive cubicle.

Frequently asked questions

What are the key electrical ratings for 4EP4002-3DS00?

3-phase, 400V AC, 50Hz. Maximum continuous current 91A, rated current 81.9A, DC-rated value 111.5A. Inductance 0.31mH with a 4% inductive voltage drop. Coil power loss 72.6W, iron-core loss 35.8W.

What approvals does 4EP4002-3DS00 carry?

It is UL/CSA-recognized per EN 61558-2-20. Thermal class B (130°C) per IEC 60085. Ambient temperature rating 40°C.

Where can I buy 4EP4002-3DS00 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here.

Will 4EP4002-3DS00 drop into a panel specified around a miniature circuit breaker like 5SJ3140-7?

No — this is a 3-phase commutating choke (line reactor) for converter input, not a circuit breaker. It is panel-mount with flat-type terminals, not DIN-rail snap-on. It serves a completely different function and wiring scheme.

MPN
4EP4002-3DS00