Skip to main content
Siemens 4EP4002-3DS00 — Line/Load Reactors

Siemens 4EP4002-3DS00 Commutating Choke, 91A, 400V, 3-Phase

MPN4EP4002-3DS00

Siemens 4EP4 series commutating choke for converters, 4EP4002-3DS00, 3-phase, 400V AC, 50Hz, 91A max / 81.9A rated, 0.31mH, IP00, flat-type terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP4002-3DS00 — Inductance & Impedance
ParameterValue
Rated inductance0.00031H
Relative inductive voltage drop4%

Identification

4EP4002-3DS00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EP4002-3DS00 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Rated current (DC)111.5A
Voltage typeAC
Rated operating frequency50Hz

Losses & Thermal

4EP4002-3DS00 — Losses & Thermal
ParameterValue
Power loss, coil (W)72.6W
Power loss, iron core (W)35.8W
Rated ambient temperature40°C

Approvals

4EP4002-3DS00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP4002-3DS00 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.179m
Width0.219m
Depth0.143m

Product details

What this choke is and where it fits

The Siemens 4EP4002-3DS00 is a 3-phase commutating choke (line reactor) for converter applications, rated 400V AC at 50Hz. It handles a maximum continuous current of 91A and a rated current of 81.9A, with a DC-rated value of 111.5A. The inductance is 0.31mH, and the relative inductive voltage drop is 4% at rated current, frequency, and voltage — a standard value for limiting current rise and harmonics on the line side of a drive.

Key ratings and what they mean for your drive line

The 91A maximum current (81.9A rated) and 111.5A DC rating tell you this choke is sized for a drive drawing around 75–90A continuous on the line side. The 4% inductive voltage drop is typical for a commutating choke — it provides enough impedance to smooth commutation notches and limit di/dt without dropping excessive voltage under load. The 72.6W coil loss plus 35.8W iron-core loss (108.4W total at rated conditions) is heat that must be dissipated; with IP00, the choke is open-frame and relies on cabinet airflow — no enclosure to trap heat, but also no protection from dust or accidental contact.

Physical fit and panel integration

Dimensions: 0.219m wide, 0.179m high, 0.143m deep. This is a panel-mount component, not a DIN-rail snap-on — it bolts into the cabinet. The 0.143m (143mm) depth is the front-to-back dimension; allow clearance for the flat-type terminal connections and bending radius of the incoming cables. IP00 means no finger-safe enclosure, so it belongs behind a locked panel door or inside a dedicated drive cubicle.

Frequently asked questions

What are the key electrical ratings for 4EP4002-3DS00?

3-phase, 400V AC, 50Hz. Maximum continuous current 91A, rated current 81.9A, DC-rated value 111.5A. Inductance 0.31mH with a 4% inductive voltage drop. Coil power loss 72.6W, iron-core loss 35.8W.

What approvals does 4EP4002-3DS00 carry?

It is UL/CSA-recognized per EN 61558-2-20. Thermal class B (130°C) per IEC 60085. Ambient temperature rating 40°C.

Where can I buy 4EP4002-3DS00 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here.

Will 4EP4002-3DS00 drop into a panel specified around a miniature circuit breaker like 5SJ3140-7?

No — this is a 3-phase commutating choke (line reactor) for converter input, not a circuit breaker. It is panel-mount with flat-type terminals, not DIN-rail snap-on. It serves a completely different function and wiring scheme.

MPN