Skip to main content
Siemens 4EP4005-8DB00 — Line/Load Reactors

Siemens 4EP4005-8DB00 Mains Choke, 600V 60Hz 0.93A 3-Phase

MPN4EP4005-8DB00

Siemens 4EP4005-8DB00 Netzdrossel (mains choke), 600V AC, 60Hz, 0.93A rated / 1.03A max, 0.795H, IP00, thermal class B, screw/tab terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP4005-8DB00 — Inductance & Impedance
ParameterValue
Rated inductance0.795H
Relative inductive voltage drop89%

Identification

4EP4005-8DB00 — Identification
ParameterValue
Product designationNetzdrossel

Electrical

4EP4005-8DB00 — Electrical
ParameterValue
Rated operating voltage600V
Number of phases3
Voltage typeAC
Rated operating frequency60Hz

Losses & Thermal

4EP4005-8DB00 — Losses & Thermal
ParameterValue
Power loss, coil (W)38.5W
Power loss, iron core (W)14W
Rated ambient temperature50°C

Approvals

4EP4005-8DB00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP4005-8DB00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals / tab terminals
IP protection ratingIP00
Height0.179m
Width0.219m
Depth0.143m

Product details

What this part is and what it does

The Siemens 4EP4005-8DB00 is a 3-phase mains choke (Netzdrossel) rated for 600V AC at 60Hz. It carries a rated current of 0.93A with a maximum of 1.03A and an inductance of 0.795H. The relative inductive voltage drop sits at 89% on the measurement level — that high drop tells you this choke is sized to provide significant impedance, which means it's intended for harmonic mitigation or current-limiting duty in a power circuit, not just a small filter reactor.

Where it goes and how it connects

This choke is IP00 — no enclosure, so it mounts inside a panel or cabinet. The screw-type and tab terminals accept the main current circuit wiring. Coil losses are 38.5W and iron-core losses add 14W, for a total heat dissipation around 52.5W at full load. That's not negligible — the panel designer needs to account for that thermal load in the cabinet ventilation, especially since the choke is IP00 and relies on the surrounding air for cooling.

What the ratings mean for fit

The 0.93A rated current at 600V 60Hz sets the continuous load limit. The 1.03A maximum is the thermal limit — do not size the choke for a motor FLA above 0.93A continuous. The 89% inductive drop means this is not a standard line reactor for general harmonic filtering; it is a high-impedance choke for specialized applications like precharge circuits or current-limiting in low-power drives. If you need a standard 3–5% impedance line reactor for a 1A drive, this is the wrong part.

Frequently asked questions

What compliance documentation is available for 4EP4005-8DB00?

The part is designed to EN 61558-2-20. The evidence does not list specific RoHS, REACH, UL, or IEC certificates — verify with the supplier at quote time.

Will 4EP4005-8DB00 drop into a panel specified for 5SQ2270-2YA04?

No — 5SQ2270-2YA04 is a SENTRON MCB (miniature circuit breaker), a completely different component class. The 4EP4005-8DB00 is a 3-phase mains choke with screw/tab terminals, IP00, and a 0.143m depth. It will not fit the same DIN-rail footprint or serve the same function.

MPN