Skip to main content
Siemens 4EP4010-0LS30 — Line/Load Reactors

Siemens 4EP4010-0LS30 Mains Choke, 80 A, 0.26 mH, 500 V AC

MPN4EP4010-0LS30

Siemens SENTRON 4EP4010-0LS30 mains choke (Netzdrossel), 3-phase AC, 80 A maximum, 0.26 mH, 500 V AC, IP00, thermal class B, free cable endings.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP4010-0LS30 — Inductance & Impedance
ParameterValue
Rated inductance0.00026H
Relative inductive voltage drop3%

Identification

4EP4010-0LS30 — Identification
ParameterValue
Product designationNetzdrossel

Electrical

4EP4010-0LS30 — Electrical
ParameterValue
Rated operating voltage500, 500V
Number of phases3
Voltage typeAC
Rated operating frequency60 ... 50Hz

Losses & Thermal

4EP4010-0LS30 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C

Approvals

4EP4010-0LS30 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP4010-0LS30 — Mechanical
ParameterValue
Main-circuit connection typefree cable endings
IP protection ratingIP00
Height0.179m
Width0.219m
Depth0.143m

Other specifications

4EP4010-0LS30 — Other specifications
ParameterValue
Rated value72A

Product details

What it is and what the ratings mean

The Siemens 4EP4010-0LS30 is a 3-phase mains choke — a Netzdrossel — rated for 80 A maximum continuous current (72 A rated value) at 500 V AC, 50/60 Hz. The 0.26 mH inductance with a 3% relative inductive voltage drop means it smooths line-side harmonics and limits inrush current for drives or converters. Thermal class B (130 °C winding rise) is standard for general-purpose industrial chokes; the IP00 enclosure means it must be mounted inside a panel or cabinet — no washdown or outdoor exposure without additional protection.

Integration and mounting

Dimensions are 0.219 m wide, 0.179 m high, 0.143 m deep. The main circuit connects via free cable endings — no terminal block, so plan for field wiring or a junction point in the panel. The choke is designed for DIN-rail or baseplate mounting inside a standard industrial enclosure. Ambient temperature rating of 40 °C is the baseline; derate above that per the thermal curve.

Frequently asked questions

Will 4EP4010-0LS30 drop into a panel specified around 5SJ3140-7 without rewiring?

No — 5SJ3140-7 is a 1-pole miniature circuit breaker with different mounting and wiring (DIN-rail, screw terminals). The 4EP4010-0LS30 is a 3-phase choke with free cable endings; it requires a different footprint and wiring plan.

MPN
4EP4010-0LS30