Skip to main content
Siemens 4EP4300-0US00 — Line/Load Reactors

Siemens SIDAC 4EP4300-0US00 Output Reactor, 34 A, 3 kHz

MPN4EP4300-0US00

Siemens SIDAC output reactor, 3-phase, 34 A AC max, 30.6 A rated, 0.25 mH, 3 kHz switching frequency, IP00, screw terminals, UL/CSA recognized.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EP4300-0US00 — Inductance & Impedance
ParameterValue
Rated inductance0.00025H

Identification

4EP4300-0US00 — Identification
ParameterValue
Product designationoutput reactor

Electrical

4EP4300-0US00 — Electrical
ParameterValue
Rated current (AC)30.6A
Number of phases3
Current (AC), max.34A
Voltage typeAC

Losses & Thermal

4EP4300-0US00 — Losses & Thermal
ParameterValue
Power loss, coil (W)76W
Power loss, iron core (W)54.7W
Rated ambient temperature40°C

Approvals

4EP4300-0US00 — Approvals
ParameterValue
Thermal class (IEC 60085)B

Mechanical

4EP4300-0US00 — Mechanical
ParameterValue
Main-circuit connection typescrew-type terminals
IP protection ratingIP00
Height0.22m
Width0.26m
Depth0.12m

Product details

Output reactor for variable-frequency drives

The Siemens SIDAC 4EP4300-0US00 is a 3-phase output reactor rated for a maximum AC current of 34 A at 120 Hz and a rated operational current of 30.6 A. Its 0.00025 H inductance and 3 kHz switching frequency are sized to protect motor windings and cable insulation from reflected-wave voltage spikes on long drive-to-motor runs. Mounts via screw terminals (IP00 enclosure), so it lands inside a panel or cabinet — not on the machine itself. The thermal class B insulation (130 °C rise) and 76 W coil loss plus 54.7 W iron-core loss mean the reactor sheds about 131 W total at full load; plan for that heat in the enclosure's ventilation budget.

Integration considerations

At 0.26 m wide, 0.22 m tall, and 0.12 m deep, the reactor occupies a compact footprint for its 34 A rating. Screw-type main-circuit terminals accept standard power wiring; no special lug kit required. Rated for a 40 °C ambient with thermal class B insulation. If the enclosure ambient exceeds 40 °C, derate the continuous current per the manufacturer's thermal curve — the 30.6 A rated operational current is the baseline at that temperature.

MPN
4EP4300-0US00