Skip to main content
Siemens 4EU2422-0BA00-0AA0 — Line/Load Reactors

Siemens 4EU2422-0BA00-0AA0 Commutating Choke, 81.9 A, 0.33 m

MPN4EU2422-0BA00-0AA0

Siemens 4EU2422-0BA00-0AA0 commutating choke (line reactor) for converter, 3-phase, 500 V AC, 50 Hz, 81.9 A rated, 0.33 mH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2422-0BA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00033H
Relative inductive voltage drop4%
4EU2422-0BA00-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU2422-0BA00-0AA0 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Rated current (DC)111.5A
Voltage typeAC
Rated operating frequency50Hz
Peak current114A
4EU2422-0BA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)122W
Power loss, iron core (W)32W
Rated ambient temperature40°C
4EU2422-0BA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2422-0BA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.136m

Product details

The Siemens 4EU2422-0BA00-0AA0 is a 3-phase commutating choke (line reactor) for converter applications, rated at 81.9 A continuous with a maximum of 91 A and a peak current of 114 A. It operates at 500 V AC, 50 Hz, with a rated inductance of 0.33 mH and a relative inductive voltage drop of 4%.

The 81.9 A rated current (I LN) is the continuous thermal current at 40 °C ambient — size your drive's input for this, not the 91 A maximum. The 114 A peak handles short-duration inrush or transient loads without saturating the core. The 4% voltage drop at rated current is typical for a commutating choke; it limits di/dt during converter switching and reduces harmonic distortion on the line side. The 0.33 mH inductance value is what governs the dV/dt smoothing — match it to your drive's DC-link design. Class H insulation and 122 W coil loss plus 32 W iron loss mean this choke runs hot. The IP00 open-frame construction requires mounting inside a ventilated enclosure.

This is a panel-mount component, not DIN-rail. Dimensions are 0.225 m wide, 0.21 m high, 0.136 m deep. Terminals are flat-type connectors for the main current circuit — expect ring lugs or bus-bar connections, not spring-cage. Designed for converter input or output duty per EN 61558-2-20. The 3-phase, 500 V AC, 50 Hz rating matches standard European industrial supply. Verify your drive's nominal voltage and frequency match before specifying.

Frequently asked questions

What compliance documentation does this part carry?

The part is designed to EN 61558-2-20 for commutating chokes. The evidence does not list RoHS, REACH, UL, or IEC specific certifications — verify with the manufacturer or your compliance team for your jurisdiction.

What are the key dimensions of 4EU2422-0BA00-0AA0?

Width 0.225 m, height 0.21 m, depth 0.136 m. This is an open-frame (IP00) component requiring panel or chassis mounting, not DIN-rail.

MPN