Skip to main content
Siemens 4EU2431-2UA00-0A — Line/Load Reactors

Siemens SIDAC 4EU2431-2UA00-0A Output Reactor, 34A 300Hz 3-P

MPN4EU2431-2UA00-0A

Siemens SIDAC output reactor, 3-phase, 575V, 34A max at 300Hz, 0.47mH, IP00, flat-type terminals, UL/CSA recognized.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EU2431-2UA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.00047H
4EU2431-2UA00-0A — Identification
ParameterValue
Product designationoutput reactor
4EU2431-2UA00-0A — Electrical
ParameterValue
Rated current (AC)30.6A
Number of phases3
Current (AC), max.34A
Voltage typeAC
4EU2431-2UA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)110W
Power loss, iron core (W)81.9W
Rated ambient temperature40°C
4EU2431-2UA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2431-2UA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.21m
Width0.22m
Depth0.13m

Product details

The Siemens SIDAC 4EU2431-2UA00-0A is a 3-phase output reactor (output choke) rated for 575 V AC, carrying a maximum continuous current of 34 A at 300 Hz switching frequency. Its rated operational current is 30.6 A, with an inductance of 0.47 mH and a voltage drop (UK) of 9%. This reactor sits between a variable-frequency drive output and the motor cable to limit dv/dt stress, reduce capacitive charging currents in long cable runs, and protect motor windings from reflected wave voltage spikes — a common concern on 400 V and 480 V class drives with cable lengths beyond about 50 meters. Built to EN 61558-2-20 and UL/CSA recognized, it carries Class H insulation (180 °C thermal class per IEC 60085) and is rated for a 40 °C ambient. Total power loss splits between the coil (110 W) and iron core (81.9 W) — roughly 192 W at full load, which must be considered in enclosure thermal calculations for the panel.

This is an open-frame (IP00) component with flat-type terminals for the main circuit connections — no DIN-rail clip, no enclosure. It measures 0.22 m wide × 0.21 m high × 0.13 m deep. Mount it on a backplate or chassis inside a panel, with clearance for airflow around the core. The flat terminals accept lug or bus-bar connections; plan for adequate bending radius on the motor cable leads.

Frequently asked questions

What are the key ratings for 4EU2431-2UA00-0A?

3-phase output reactor rated 575 V AC, 34 A maximum at 300 Hz switching frequency, 30.6 A rated operational current, 0.47 mH inductance, 9% voltage drop, Class H insulation, 40 °C ambient, IP00 open-frame with flat-type terminals.

What compliance documentation does this reactor carry?

It is built to EN 61558-2-20 and is UL/CSA recognized, as stated in the product description.

Where can I buy 4EU2431-2UA00-0A and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
4EU2431-2UA00-0A