Siemens 4EU2432-0EB00-0AA0 — Line/Load Reactors

Siemens SIDAC 4EU2432-0EB00-0AA0 Output Reactor, 360 A, 0.01

MPN4EU2432-0EB00-0AA0

Siemens SIDAC output reactor, 3-phase, 360 A, 0.012 mH, 4.6 kHz switching frequency, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2432-0EB00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000012H
4EU2432-0EB00-0AA0 — Identification
ParameterValue
Product designationoutput reactor
4EU2432-0EB00-0AA0 — Electrical
ParameterValue
Number of phases3
Voltage typeAC
4EU2432-0EB00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)163W
Power loss, iron core (W)50W
Rated ambient temperature45°C
4EU2432-0EB00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2432-0EB00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.21m
Width0.22m
Depth0.13m

Product details

What this output reactor does on the line

The Siemens SIDAC 4EU2432-0EB00-0AA0 is a 3-phase output reactor rated for 360 A continuous at 690 V, with an inductance of 0.012 mH. It sits between the VFD output and the motor leads, filtering the PWM carrier to reduce motor insulation stress and bearing currents. The 4.6 kHz rated switching frequency matches common IGBT drive stages; if your drive runs a higher carrier, the reactor still attenuates but derate the current per the thermal curve above 45 °C ambient.

Fit and mounting reality

IP00 — no enclosure, so this mounts inside a panel or cabinet, not exposed. Dimensions are 0.22 m wide by 0.21 m tall by 0.13 m deep; plan for clearance around the flat-type terminals on the main circuit connection. Thermal class H per IEC 60085 means the winding insulation handles 180 °C hot-spot, which is typical for reactor duty in a closed cabinet with limited airflow. The iron-core loss of 50 W plus coil loss of 163 W total 213 W heat to vent; don't bury it against the backplate without a path out.

Frequently asked questions

Where can I buy 4EU2432-0EB00-0AA0 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key electrical ratings for this output reactor?

It is a 3-phase AC reactor rated for 360 A continuous, 0.012 mH inductance, with a rated switching frequency of 4.6 kHz and a maximum operating voltage of 690 V.

What compliance documentation does this reactor carry?

The nameplate indicates UL/CSA recognition and compliance with EN 61558-2-20, the safety standard for chokes and reactors.

MPN
4EU2432-0EB00-0AA0