Its 0.25 mH inductance limits the dV/dt and current ripple on the motor cable, protecting the drive output stage and reducing bearing currents on long cable runs. Thermal class H insulation (IEC 60085) allows a 40 °C ambient with the listed iron-core loss of 79.4 W and coil loss of 110 W, so panel ventilation must account for that total 189.4 W dissipation.
Integration notes
Dimensions: 0.22 m wide × 0.21 m tall × 0.13 m deep. The main circuit connection uses flat-type terminals, suited for busbar or lug connections rather than spring-cage or screw-clamp wire terminals. IP00 requires the reactor to live inside a grounded metal enclosure with adequate clearance to live parts. The 8 kHz switching frequency matches most IGBT-based drive output stages; verify that the drive's PWM carrier frequency does not exceed this rating.