Skip to main content
Siemens 4EU2432-0EL00-4CA0 — Line/Load Reactors

Siemens 4EU2432-0EL00-4CA0 Filter Reactor, 25 kVAR, 590 V, 5

MPN4EU2432-0EL00-4CA0

Siemens 4EU2432-0EL00-4CA0, 3-phase filter reactor, 25 kVAR, 590 V, 50 Hz, 7% impedance, 189 Hz resonant frequency, IP00 enclosure, screw terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Product details

3-Phase Filter Reactor, 25 kVAR, 590 V, 50 Hz

The Siemens 4EU2432-0EL00-4CA0 is a 3-phase filter reactor rated for 25 kVAR at 590 V, 50 Hz, with a 7% impedance and a resonant frequency of 189 Hz. Built to EN 61558-2-20, it serves as a line-reactor choke in power-quality and harmonic-mitigation applications — typically placed between a drive and the supply to limit current rise and reduce harmonic distortion. The IP00 rating means it is an open-frame component intended for installation inside a cabinet or enclosure, not for standalone outdoor use. Termination is via screw connections, which suits panel wiring practices where ring or fork terminals are preferred over bus-bar clamps.

The 25 kVAR rating at 590 V defines the reactive-power compensation capacity — this reactor is sized for a specific harmonic filter bank or drive input section, not a general-purpose line choke. The 7% impedance (P(%):7) is the per-unit voltage drop at rated current, which governs how much harmonic attenuation the reactor provides; 7% is a common choice for 6-pulse drive front ends to meet IEEE 519-2014 guidelines. The 189 Hz resonant frequency tells you where the reactor's impedance peaks — important when tuning a filter to avoid resonance with downstream capacitor banks or system harmonics. The 40 °C ambient rating (TA/ISOKL:40 /H) is the maximum operating temperature; derate current above that.

The IP00 enclosure means this reactor must be mounted inside a cabinet with appropriate clearance for airflow and creepage distances. Screw terminals accept standard ring or fork lugs; torque values per Siemens installation instructions. The 40 °C ambient rating governs the thermal design of the enclosure — ensure adequate ventilation or forced cooling if the cabinet ambient exceeds that. No DIN-rail clip is specified; expect foot-mounting on a panel or chassis base.

Frequently asked questions

Where can I buy the 4EU2432-0EL00-4CA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quotation; availability and current pricing are confirmed at quote time.

What does the 7% impedance rating mean for this filter reactor?

The 7% impedance (P(%):7) is the per-unit voltage drop at rated current. It determines the harmonic attenuation level — 7% is typical for 6-pulse drive input sections to meet IEEE 519 harmonic limits. Higher impedance gives more attenuation but also more voltage drop under load.

What is the resonant frequency of the 4EU2432-0EL00-4CA0?

The resonant frequency is 189 Hz. This is the frequency at which the reactor's impedance peaks, critical for avoiding parallel resonance with power-factor correction capacitors or system harmonics.

What compliance documentation is available for this reactor?

The reactor is built to EN 61558-2-20, the standard for chokes and reactors. For RoHS, REACH, and UL documentation, request the Siemens declaration of conformity at the time of quotation — these are typically available per batch or serial number.

MPN
4EU2432-0EL00-4CA0