Siemens 4EU2451-2UA00-0A — Line/Load Reactors

Siemens 4EU2451-2UA00-0A Mains Choke, 160 A, 3-Phase, 400/48

MPN4EU2451-2UA00-0A

Siemens 4EU2451-2UA00-0A mains choke (Netzdrossel f. FU), 3-phase, 400/480 VAC, 160 A max / 144 A rated, 0.088 mH, 2% voltage drop, IP00, Class H, flat-type terminals.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EU2451-2UA00-0A specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value400, 480V
Relative inductive drop in voltage on the measurement level current, voltage and frequency2%
Power loss [W] of the coil120W
Operating frequency rated value50 ... 60Hz
Phase number3
Ambient temperature rated value40°C
Depth0.147m
Width0.225m
Height0.21m
Thermal class acc. to IEC 60085H
Rated value144A
Protection class IPIP00
Inductivity rated value0.000088H

Product details

The Siemens 4EU2451-2UA00-0A is a three-phase mains choke (line reactor) designed for installation ahead of a variable-frequency drive (VFD). It smooths the input current, limits harmonic distortion, and protects the drive's DC bus from line transients. Rated for 400/480 VAC at 50/60 Hz, it carries a maximum continuous current of 160 A and a rated current of 144 A — the figure you use for sizing against your motor load. That 2% figure is the design target: it's enough to suppress harmonics without dropping excessive voltage across the choke under load.

This is an IP00 open-frame choke — no enclosure, no finger-safe covers. Dimensions are 0.225 m wide, 0.21 m high, and 0.147 m deep; plan your gland plate and DIN-rail layout accordingly, though the choke itself bolts to a mounting plate rather than snapping onto a rail. The main circuit connects via flat-type terminals — expect bus-bar or cable-lug terminations, not spring-cage or screw-clamp. Verify your lug width and bolt size against the terminal opening before panel assembly.

Thermal and insulation class

Rated for a 40 °C ambient, the coil dissipates 120 W at full load. Class H insulation (180 °C rated) gives a generous thermal margin — the choke can run hot without degrading the winding insulation, which matters in a crowded panel where airflow is restricted.

Frequently asked questions

What is the 4EU2451-2UA00-0A used for?

It is a three-phase mains choke (line reactor) installed ahead of a variable-frequency drive to limit harmonic distortion, smooth input current, and protect the drive's DC bus from line transients.