Skip to main content
Siemens 4EU2452-1UA00-0AA0 — Line/Load Reactors

Siemens 4EU2452-1UA00-0AA0 Mains Choke for VFD, 140 A, 0.13

MPN4EU2452-1UA00-0AA0

Siemens Netzdrossel f. FU, 3-phase mains choke, 500 V AC, 140 A max / 126 A rated, 0.13 mH, IP00, UL/CSA recognized, order code 4EU2452-1UA00-0AA0.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2452-1UA00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00013H
Relative inductive voltage drop2%
4EU2452-1UA00-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU2452-1UA00-0AA0 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU2452-1UA00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)125W
Power loss, iron core (W)27W
Rated ambient temperature40°C
4EU2452-1UA00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2452-1UA00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.21m
Width0.225m
Depth0.147m

Product details

FU" tells you exactly that. It sits between the supply and the drive's rectifier, smoothing current harmonics and limiting inrush. This is an open-frame (IP00) component — no enclosure, no finger-safe terminals. It mounts inside a panel, not on a wall. The flat-type terminals for the main circuit are sized for lug or bus-bar connections, so plan for a bolted interface rather than a spring-cage or screw-clamp. Thermal class H insulation (180 °C) per IEC 60085 means the coil can run hot without degrading the magnet wire — that matters when the choke is pulling full current inside a warm cabinet.

Power loss and thermal budget

Total power loss splits into 125 W from the coil (copper losses) and 27 W from the iron core (hysteresis and eddy-current losses), for a combined 152 W at rated load. At 40 °C ambient, the choke is at its rated thermal capacity — push the cabinet temperature higher and you'll need to derate current or add forced airflow.

Dimensions for panel layout

Footprint is 0.225 m wide by 0.21 m tall, with a depth of 0.147 m. That's a substantial block — roughly 9 by 8 by 6 inches — so it needs dedicated real estate on the backplate or a mounting shelf. Not a DIN-rail snap-on; it bolts down.

Frequently asked questions

Where can I buy 4EU2452-1UA00-0AA0 and how is it quoted?

This part is sourced to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ — no stock count or price is listed here.

What compliance documentation does 4EU2452-1UA00-0AA0 carry?

The part is UL/CSA recognized per the manufacturer's description, and it's designed to EN 61558-2-20. That covers North American listing and the relevant IEC standard for chokes.

What does the 2% voltage drop mean for my drive?

The 2 % relative inductive voltage drop at rated current is typical for a drive input reactor. It provides enough impedance to reduce harmonic current distortion without dropping excessive voltage that would starve the drive's DC bus under load.

MPN
4EU2452-1UA00-0AA0